Device Status Indicators

Test & Reset Installation

Failure Modes & Quick Repair

LED signals

Power LED:
•  BLUE = device is powered and in operation
Bus A/Bus B:
•  BLUE = Bus status is ok
•  Blinking BLUE = communication on the Bus
•  RED = Bus error (short)
•  Blinking RED = More device than allowed on the Bus
•  Blinking PURPLE = Bus test in progress
•  Continuous PURPLE = PB1/2 push is active

Status:
•  Continuously blinking BLUE = status OK
•  Blinking blue quickly = Controller is booting or busy
•  Blinking purple slowly = Controller is searching for  

    endpoints
•  Continuous BLUE or OFF = Controller is frozen, perform  

    a reset
•  Blinking red quickly = TLS handshake / Authentication

TEST of connected devices

•  PB1 (pushbutton 1) short press: start testing Bus A bus:

  lamps start dimming up and down on the bus until  

  another short press is performed or 5-minute timer is  

  expired. Meanwhile ‘Bus A’ LED is blinking purple.
•  PB2 (pushbutton 2) short press: start testing Bus B bus:

  lamps start dimming up and down on the bus until  

  another short press is performed or 5-minute timer is  

  expired. Meanwhile ‘Bus B’ LED is blinking purple.

 

RESET functionalities

•        (reset button) short press: restart controller (HW reset,

  no software configuration impact)
•  PB1 long press (min 10 seconds): reset all Digital devices,

  control gears + other devices to reset value on Bus A
•  PB2 long press (min 10 seconds): reset all Digital devices,

  control gears + other devices to reset value on Bus B
•  PB1 + PB2 Long press (min 10 seconds) = reset controller  

  to factory defaults: empty flash configuration database,  

  reset passwords and run self-test. All indicator LEDs blink  

  4 times when device reset.

Real Time Clock

In case of power outage controller can keep the set internal clock. Retention time: 1 week.

#  Statement 

Take action

1

  Controller do not react on buttons and status LED is continuous 

Push reset button or power off and

  BLUE or OFF.  

on device 

2

  If Bus A/B indicator LED is continuously RED, then Bus error. 

Check Digital bus wiring voltage drop,

   

wiring short circuit or endpoint limitation

3

  If Bus A/B indicator LED is Blinking RED, then controller has more 

Check Digital device limitation 

  Digital device on the bus than allowed
4

  If two lamps work together than the same short address was set. 

Reprogram driver or reset Bus A or B by    

   

long-press on PB 1 or 2

5

  If the power indicator LEDs flashing up blue for a few second and 

The controller cannot be repaired locally.

  then all indicator LEDs are dark. 

Contact GE support.

6

  If all indicator LEDs are dark. 

Check supply voltage. Contact GE support.

Содержание Lightsweep

Страница 1: ...s en veiligheidsinformatie kan op de volgende locatie worden gevonden ET Eestikeelse paigaldusjuhendi ja ohutusn uded leiate aadressilt EN The English version of the installation instruction and safet...

Страница 2: ...tal Interface Two independent digital communication and power supply interface The power supply is feeding 18 5V 175mA DC 10 it has electrical current limitation and protection against overheating and...

Страница 3: ...pendently Mounted Control for panel mounting Type of action and additional features Type 1 Control Pollution Degree 2 Software Class and Structure Class A Rated Impulse Voltage 2500 Marking Definition...

Страница 4: ...amps start dimming up and down on the bus until another short press is performed or 5 minute timer is expired Meanwhile DIGITAL A B LED is blinking purple Strip wires as shown on illustration Mains 11...

Страница 5: ...eparation of circuits Warning the wiring shall be installed in accordance with National Electric Code and local codes rules the power wiring must be separated accordingly from the class 2 signal wirin...

Страница 6: ...software configuration impact PB1 long press min 10 seconds reset all Digital devices control gears other devices to reset value on Bus A PB2 long press min 10 seconds reset all Digital devices contro...

Страница 7: ...gn or typical values when measured under laboratory conditions Current powered by GE is a business of the General Electric Company 2018 GE www currentbyge com CTRL020 Rev 09 05 18 Legal Disclaimer For...

Отзывы: