Connecting Digital Devices

Network Connectivity

Cable length limitations, Digital bus (control interfaces in accordance with 15.5 of IEC 61347-2-3:2011):

Conductor x-section, AWG/mm

2

, copper

 18/.75  17/1 

15/1.5 

14/2 

12/3*

Cable length, ft./m

 

310/95 390/120 620/190 790/240  1250/375*

*overall cable length above 1000ft/300m shall be avoided

DC resistance must not exceed 4Ω; according to IEC62386-101:2014.

Both Electrical and Logical limitations of Digital bus shall be considered when sizing / designing of the lighting control system.

Wiring Relay outputs

Maximum cable length of relay outputs: DC resistance must not exceed 10Ω (see table below)

Cable length limitations, relay drive outputs: 

Conductor x-section, AWG/mm

2

, copper

 30/.05  26/.125  23/.25 

17/1 

14/2 

12/3

Cable length, ft./m

 

40/12 100/30 250/75 1000/300 2000/600 3000/900

Wiring Input interfaces on controller

Warning

: negative terminals are common internally. Loops should be avoided

Maximum cable length for inputs: wiring DC resistance must not exceed 100Ω

Cable length limitations, analog control inputs (negative terminals are common internally): 

Conductor x-section, AWG/mm

2

, copper

 30/.05  26/.125  23/.25**  17/1** 

14/2** 

12/3**

Cable length, ft./m

 

500/150 1200/375 2500/750 10000/3000 20000/6000 31000/9000

**care should be taken applying cable lengths above 1650ft/500m as it can harmfully influence stability.

Separation of circuits

Warning

: the wiring shall be installed in accordance with National Electric Code and local codes rules; the power wiring 

must be separated accordingly from the class 2 signal wiring

Power wiring - AC power input and the relay outputs

Signal wiring - Ethernet, input interfaces and Digital Bus A/B

Electrical limitations of each Digital bus
Max current load on each bus = 175mA

When connecting devices calculate power consumption of 

the devices on the bus
•  Control Gear: 2 mA**
•  Lightsweep™ Digital Switch Interface: 2 mA
•  Lightsweep™ Digital Multisensor 2: 3 mA

Logical limitations of each Digital bus
•  Max number of Digital control gears applicable per bus: 64 pcs
•  Max number of Digital input devices applicable per bus: 64 pcs
Input devices are GE Digital switches and sensors. In terms 

of connecting 3rd party Digital devices please contact 

support.

Lightsweep™ system requires wired network for operation 

and wireless (Wi-Fi) network for commissioning and setup 

(In case of standalone deployment, this can be a temporary 

network).

Lightsweep™ devices should be placed into an independent 

broadcast domain in the network, separated from any other 

devices and communications. These Controllers can obtain 

their IP addresses with DHCP, therefore an active IPv4 DHCP 

service should be available in this network segment. Static 

IP addresses are not supported.

The hand held device with the commissioning application 

should be connected to the same network segment. The 

proper Wi-Fi coverage in the whole commissioning area is 

an essential need.

Содержание Lightsweep

Страница 1: ...s en veiligheidsinformatie kan op de volgende locatie worden gevonden ET Eestikeelse paigaldusjuhendi ja ohutusn uded leiate aadressilt EN The English version of the installation instruction and safet...

Страница 2: ...tal Interface Two independent digital communication and power supply interface The power supply is feeding 18 5V 175mA DC 10 it has electrical current limitation and protection against overheating and...

Страница 3: ...pendently Mounted Control for panel mounting Type of action and additional features Type 1 Control Pollution Degree 2 Software Class and Structure Class A Rated Impulse Voltage 2500 Marking Definition...

Страница 4: ...amps start dimming up and down on the bus until another short press is performed or 5 minute timer is expired Meanwhile DIGITAL A B LED is blinking purple Strip wires as shown on illustration Mains 11...

Страница 5: ...eparation of circuits Warning the wiring shall be installed in accordance with National Electric Code and local codes rules the power wiring must be separated accordingly from the class 2 signal wirin...

Страница 6: ...software configuration impact PB1 long press min 10 seconds reset all Digital devices control gears other devices to reset value on Bus A PB2 long press min 10 seconds reset all Digital devices contro...

Страница 7: ...gn or typical values when measured under laboratory conditions Current powered by GE is a business of the General Electric Company 2018 GE www currentbyge com CTRL020 Rev 09 05 18 Legal Disclaimer For...

Отзывы: