background image

7

GG-CO2

Operation

Start-up

Before applying power, make a final check of all wiring 

for continuity, shorts, grounds, etc.  After power-up, 

allow at least 2 hours for the system to stabilize before 

testing the sensors.  Because sensors are normally 

located at a distance from the main unit, the test 

time required and accuracy of the response checks 

will be improved if two people perform the start-up 

procedures and use radio contact.

Start-Up Test:

1) One person exposes each sensor to calibration gas. 

(breathing on the sensor can also produce a significant 

signal rise)
2) The second person stays at the control unit to 

determine that each sensor, when exposed to 

carbon dioxide, is connected to the proper input and 

responds, causing appropriate alarm functions.

Calibration

The GG-CO2 Sensor comes factory calibrated and 

should require only minimal adjustments after 

installation. There are two pots on the preamp that 

are used for calibration.

Note:  Never measure sensor output in mA .  

Always use mVDC (or VDC) voltmeter settings .

Zero Calibration:

 After the unit is installed and has 

been powered up for a minimum of 2 hours, the unit 

can be zero calibrated by the following:
•  Apply 500 ppm CO

2

 gas at 0.5 to 0.8 L/min.

•  Adjust the zero pot until the voltmeter reads the 

following mVdc on the test points [-] to [+] (see 

Figure 2).

•  0-1% CO

2

 range sensor = 48.0 mVdc

•  0-3% CO

2

 range sensor = 42.7 mVdc

•  0-5% CO

2

 range sensor = 41.6 mVdc

Span Calibration: 

If span adjustment is required, the 

following procedure will span the unit:
•  Perform zero calibration prior to spanning.
•  Connect tubing to the calibration port of the 

infrared tube. (see Figure 2)

•  Apply span gas at 0.5 to 0.8 L/min.
•  Sensor should react to gas within 10 seconds.
•  Once the output signal has peaked (or two minutes 

maximum) adjust the span pot until the correct 

output is achieved with full-scale span gas, the 

calculated span value will be 200 mVdc.  

Note: The adjustment response is dampened.  Make 

slight adjustments (no more than ½ turn of the 

potentiometer) and wait for output response.  
If the correct output cannot be achieved, contact 

Calibration Technologies for technical help.

Содержание GG-CO2

Страница 1: ...Installation and Operation Manual GG CO2 CARBON DIOXIDE GAS SENSOR...

Страница 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Страница 3: ...920 N Tradewinds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6 Oper...

Страница 4: ...cycles etc The circuit board is sealed in potting compound completely protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant polycarbonat...

Страница 5: ...variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws should be screwed into the studs Mount sensor enclosur...

Страница 6: ...elded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections should be soldered Ground...

Страница 7: ...asure sensor output in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 2 hours the unit can be zero calibrated by the...

Страница 8: ...8 GG CO2 Figure 2 Sensor output and zero span adjustments Span and Zero adjustments 40 200 mV mVDC Black Red Calibration Gas Port...

Страница 9: ...ld be performed with certified calibration gas Calibration kits and replacement cylinders are available from Calibration Technologies All tests and calibrations must be logged Always disconnect power...

Страница 10: ...cale Repeatability 1 of full scale Wiring Connections 3 conductor shielded stranded 20 AWG cable General Cable C2525A or equivalent up to 1500 ft Terminal Block Plug Field Wiring 26 12 AWG torque 4 5...

Страница 11: ...ct by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper storage ins...

Страница 12: ...ctiengineering com 866 394 5861 GG CO2 DOC1 0 20190604...

Отзывы: