GG-CO2
Installation Guidelines:
• Always mount the sensor vertically.
• Must be easily accessible for calibration and
maintenance.
• Mount the sensor close to the potential leak source.
• For optimum personnel protection, mount sensor
in the “breathing zone” (4’ – 5’ above floor).
• Take air movement and ventilation patterns into
account.
• To prevent electrical interference, keep sensor and
wire runs away from mercury vapor lights, variable
speed drives, and radio repeaters.
• Protect sensor from physical damage(forklifts, etc.).
• If mounting on a wall with studs, the mounting
screws should be screwed into the studs.
• Mount sensor enclosures through the mounting
holes as shown in Figure 1. Use the supplied
self-tapping screws for mounting on sheet metal
surfaces.
• Even though the sensor comes from the factory
calibrated, it is always a good idea to calibrate the
sensor to the environment in which it is installed.
This will compensate for any inaccuracies caused by
a change is temperature, altitude, etc.
2.0"
6.5"
6.8"
7.75"
Figure 1: Mounting Dimensions