CTI Janus Programmable Automation Controller IOG
67
Error
Code
Description
Priority
Operation
Error Recovery
510
CTI Data Cache Client: Host
PLC Fatal Error
26
Controller continues to run
normally
Clear Host PLC Fatal Error
515
CTI Data Cache Client: Host
PLC in Program Mode
29
Controller continues to run
normally
Change Host PLC mode to RUN
520
CTI Data Cache Client:
Inaccessible PLC Address
29
Controller continues to run
normally
Check that CTI Data Cache
configuration matches PLC
memory configuration
525
CTI Data Cache Client: No
Memory Buffers Available
for Data Write to Host PLC
(too many Write requests
during one Host PLC scan).
*
Controller continues to run
normally.
Error clears next IEC PLC
cycle.
Increase Host PLC time slice for
CTI Data Cache interface.
Set “fixed” IEC PLC
cycle time.
540
CAMP Client Error
(Connection to servers or
communication failed)
28
Controller continues to run
normally
Check configuration and
connection to CAMP Server(s).
550
MODBUS Client Error
(Connection to servers or
communication failed)
28
Controller continues to run
normally
Check configuration and
connection to Modbus Server(s).
560
Data Exchange Error
(Subscriber not receiving
data from
one or more
Publishers).
27
Controller continues to run
normally
Check Global Binding
configuration and connection to
Data Exchange Publisher device.
570
Ethernet/IP Scanner Error
(Connection to servers or
communication failed)
28
Controller continues to run
normally
Check configuration and
connection to EIP Adapter(s).
580
Ethernet/IP Tag Client Error
(Error is default at startup
when configured)
28
Controller continues to run
normally
Check configuration and
connection to EIP Server.
590
MQTT Client Error
(Connection to broker or
communication failed)
28
Controller continues to run
normally
Check configuration and
connection to MQTT broker.
595
NTP Server Error
(Connection to NTP Server
lost/failed)
28
Controller continues to run
normally
Check configuration and
connection to NTP Server.