6. PUMP INSTRUCTIONS
6.1.7 Suction pipe tables BFP21LE-S
6.1.7.1 Overhead Tank
One-pipe system
Height m
Line diameters
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
ø 4 mm
51
45
38
32
26
19
13
6
ø 5 mm
100 100
94
78
62
47
31
16
ø 6 mm
100 100 100 100 100
97
65
32
Two-pipe system
Height m
Line diameters
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
ø 6 mm
33
31
29
27
25
23
21
19
ø 8 mm
100
98
91
85
79
72
66
60
ø 10 mm
100 100 100 100 100 100 100 100
6.1.7.2 Underlying Tank
One-pipe system
For reliable operations, use of a Tigerloop is recommended in underlying
tanks.
Two-pipe system
Height m
Line diameters
0
-0,5 -1,0 -1,5 -2,0 -2,5 -3,0 -3,5 -4,0
ø 6 mm
17
15
13
11
9
7
5
3
1
ø 8 mm
53
47
41
34
28
22
15
9
3
ø 10 mm
100 100 99
84
68
53
37
22
6
The suction line tables comprise theoretically calculated values where
pipe dimensions and oil fl ow are adapted to prevent turbulent fl ows from
occurring. Turbulent fl ows can result in pressure losses and noise in
the pipework. A typical pipe system usually comprises pipe runs with 4
bends, a non-return valve, a shut-off valve and a pre-fi lter.
The total resistance of these items is such that it can be disregarded. In
the tables no run longer than 100 m is listed, as experience shows this
not to be required.
The tables apply to standard heating oil of normal grade merchantable
according to existing norms. When starting operations with an empty pipe
system, the pump should not be run without oil for more than 5 min. (This
presupposes that the pump is lubricated with oil when running.)
The tables give the total suction line length in meters with a nozzle capacity
of 2.5 kg/h. Max. permissible pressure on the suction and pressure lines
is 2.0 bar.
Содержание CTC 380 IC
Страница 2: ......
Страница 3: ...CTC 380 IC Models 17 19 24 29 162 105 11 1 2013 05 21...
Страница 4: ......
Страница 6: ...CTC 380 IC 6...
Страница 45: ...CTC 380 IC 45...
Страница 46: ......
Страница 52: ...7 4 6 5 3 16 18 17 21 19 22 20 14 15 7 5 6 8 9 3 4 1 2 10 23 6 2 TECHNICAL DATA 2 2 Description...
Страница 67: ...21 Boiler 8 ELECTRICAL EQUIPMENT 380IC 17 19 8 1 Wiring diagram LMO14 113...
Страница 69: ...23 Boiler 9 ELECTRICAL EQUIPMENT 380IC 24 29 9 1 Wiring diagram SATRONIC TF 834E TF 834E 2 TF834E 3...
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 161 421 50 10 01...