Important:
•
This schedule is based on average operating conditions. In some cases it may be necessary to increase
maintenance frequency.
•
Clean the condensate purge filter on the purging system 1 week after start-up.
*You must comply with the recommendations at the beginning of this chapter.
9
Alarm
When temperature sensor is broken or short circuited, the first digit point (see diagram § 5.1) will blink and the
display show value ‘’00’’. In the same time, the compressor of the drier cut off.
Replace the broken sensor by a new one (do it without tension on the drier).
After sensor has been replaced, switch on the dryer, the display will show normal temperature and the
compressor will start after the 2 minutes delay.
10
Components interns arrangement
Rep Description Rep Description
1
Thermical Mass
6
High Pressure switch
2
Compressor
7
High Pressure switch reset
3
Condenser
8
Valve + drain filter
4
Fan
9
Drain Solenoid valve
5
Low pressure switch
10
Compressor overload reset