![CSI CARDPIN1 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/csi/cardpin1/cardpin1_installation-manual_2692608023.webp)
Installation Guide
ABA Readers
CSI Readers
17
1.
Connect the white wire (Data) from the reader to terminal 3 (see
).
2.
Connect the red wire (+5 V) to terminal 4.
3.
Connect the green wire (Strobe) to terminal 5.
4.
Connect the brown wire (LED) to terminal 6 for Red LED operation, or terminal 7
for Green LED operation.
5.
Connect the black wire (GND) to terminal 8.
6.
Connect the cable shield to a good earth ground and to terminal 2 on the breakout
box.
Caution:
When connecting the reader to a DPU-7920 series controller, do
not
connect the cable
shield to terminal 2 on the DPU (TB3 or TB4). These controllers use terminal 2 as an
auxiliary input.
The cable shield
must
be connected to a good earth ground at
one
location only
. When
using a DPU-7910A series controller, you can configure the DPU to provide the neces-
sary ground by placing the jumper labeled J12 across posts A and B. This places chassis
ground at terminal 2 of the attached breakout box. You may then connect the cable shield
to terminal 2 of the breakout box.
Note:
The DPU-7920 series controllers
cannot
be configured to provide the chassis ground for the
cable shield. These controllers use terminal 2 as an auxiliary input.
Figure 11. ABA MAGSWIPEID Cable Connection
TB3 or TB4
1
2
3
4
5
6
7
8
White (DATA)
Red (+12 VDC)
Green (STROKE)
Brown (RED LED)
Brown (GREEN LED)
Black (GROUND)
From MAGSWIPEID
Reader
DPU-7920 Connections:
SHIELD
1
2
3
4
5
6
8
White (DATA)
Red (+5V)
From MAGSWIPEID Reader
Breakout Box Connections:
Brown
(GREEN LED)
Black
(GROUND)
Brown
(RED LED)
Green (STROBE)
7
SHIELD
To DPU-7910A
Series Controller