Ba tte ry Ch a rg in g
Whenever the battery begins to draw more than 100 mA out of the power supply (eg when the power
supply is first turned on or a battery is connected), the power supply measures the initial battery
current. The initial battery current is used to estimate how long the battery will need to be Boost
charged for. After Boost charging the battery for the estimated time (3-10 hours,
Vb
,
BATT CHG
and
BO
LEDs ON), the power supply will switch to Float charging (
Vb
,
BATT CHG
and
FL
LEDs ON).
Note: if the battery charging current falls below 100 mA at any stage during Boost or Float charging,
the Power Supply will stop charging the battery (
BATT CHG
,
BO
and
FL
LEDs OFF,
Vb
now flashes
every 4 seconds).
P a rt Nu m b e rs
PS-11-C
AC input, Auxiliary 24 V converter fitted
PS-11-0
AC input, Auxiliary 24 V converter not fitted
P S -11 Blo c k Dia g ra m
N
FILTER &
RECTIFIER
A
E
LED
VSUP
INTERNAL
TEMP.
SENSOR
TS
R-
EXT.
TEMP.
SENSOR
B+
B-
OPTIONAL
BATTERY
Vb
5V
0V
PCON
EARTH
LOW
VOLTAGE
CUTOFF
S1
LED
Vb
BACKPLANE
LED
LO
RS485
DRIVER
LED
OK
LED
CHG
LED
BO
LED
FL
BACKPLANE
LED
VAUX
VA+
VA-
R+
R-
RADIO
LK4
LK5
Vb
RADIO
POWER
AUX24 PWR
Isup CURRENT
MONITOR
Ibat CURRENT
MONITOR
PWR
TEMP
Ibat
Isup
BAT LOW
MONITORING
TEMPERATURE
COMPENSATION
+5V
REG.
70W
DC/DC
CONVERTER
LOW
VOLTAGE
MONITOR
MICRO CONTROLLER
ISOLATED 24V
AUXILIARY
DC/DC
CONVERTER
10W
(OPTIONAL)