background image

Troubleshooting — 9

Notes

Rev 3-97

* School

Bus cable or connectors, or it may mean an open opto-isolator at the input
device.

Crown Bus Wave Form Testing

When a loop problem exists and you have determined that the DC character-
istics of the Crown Bus are all good and that there are no breaks, it is time to
get serious and look at the data signal wave form. This check will tell you if there
is a capacitance or RFI problem on a loop.
General symptoms of a capacitance or RFI
problem on a loop would be partial or
inconsistant loop operation. In some cases it
may not be possible to establish communi-
cation at all, and in other cases ghost
components may appear at
a Roll Call that are not in the
system at all.

To perform this test you will
need to modify a loop cable
by adding a 100 ohm resis-
tor in series with the nega-
tive wire of the cable. You
will also need an oscillo-
scope to view the signal.
Signals may be generated
on the Crown Bus by run-
ning Roll Calls, loading
dataframes, or by discon-
necting a Crown Bus cable
at the input to a component
at the beginning of the loop.

Figure 5 shows a test rig
setup for wave form mea-
surement. Note that if an
ungrounded scope is used
it makes no difference
whether the resistor is in the
positive or negative leg, but
if a grounded scope is used
you must put the resistor in
the negative leg and the
negative lead of the scope
on the side of the resistor
electrically closest to the
output device.

Figure 6 shows what a good
data signal looks like. Note
that greater than 12 ma is
required for a current high
(data logic low) and current
level must drop below 4 ma
for a current low (data logic
high).

OUT

IN

+ – + –

SMX 1

OUT

IN

+ – + –

SMX 2

OUT

IN

+ – + –

SMX 3

OUT

IN

+ – + –

SMX 4

15 VDC

+

Loop is broken between SMX 2 and SMX 3.
Break Detect reports "Break Before SMX 2"
because SMX 2 senses loss of input continuity
and sends break report with component ID.
High voltage at the output driving open,
no voltage at input.

0 VDC

+

OUT

IN

+ – + –

SMX 1

OUT

IN

+ – + –

SMX 2

OUT

IN

+ – + –

SMX 3

OUT

IN

+ – + –

SMX 4

0 VDC

+

Loop is shorted between SMX 2 and SMX 3.
Break Detect reports "Break Before SMX 2"
because SMX 2 senses loss of input continuity
and sends break report with component ID.
No voltage is read at either connector due
to short. SMX 3 is protected by current limit.

0 VDC

+

Figure 3. Loop Voltage Check With Loop Open

Figure 4. Loop Voltage Check With Loop Shorted

Содержание SMX 1

Страница 1: ...ered with IQ List the configuration parameters that must match between software and interface hardware State the maximum operating length RS232 and RS422 State the maximum loop capacitance for normal...

Страница 2: ...igure 2 6 Voltage Measurement Open Figure 3 7 Voltage Measurement Reverse Polarity Figure 4 8 Current Measurement Figure 5 9 Does The Software Run PC Requirements Environment Windows DOS Corrupt or In...

Страница 3: ...e right general area for the exact problem Specifically is the process of defining the exact nature of the problem Example When taking a Roll Call all components appear except those in equipment room...

Страница 4: ...ments for the type of software being used IQ components are not likely to fail but it is not impossible Lightening is a respecter of no one The most common type of hardware failure is opto isolator da...

Страница 5: ...ponent address To save time later it is always recommended that you mark components with their loop address and annotate system drawings to accurately reflect those addresses TOOLS AVAILABLE There are...

Страница 6: ...for some reason such as power loss the On Line Search feature will automatically reestablish communication with that component when power is restored It will also restore communication to a whole loo...

Страница 7: ...ect It is a feature you would use if you were not able to establish loop communication initially you missed the alert on the screen or you want to verify the break To use Search you need to select the...

Страница 8: ...e versed If you have no voltage drop at all the problem may be an open in one of the wires between the output of the upstream device and the point of measurement as shown in Figure 3 It could alsobeas...

Страница 9: ...oop Figure 5 shows a test rig setup for wave form mea surement Note that if an ungrounded scope is used it makes no difference whether the resistor is in the positive or negative leg but if a grounded...

Страница 10: ...e prob lem may result in loss of high current or low current values When the problem isextremelyhighRFItheproblemismorelikelytobealossoflowcurrentvalues OUT IN SMX 1 OUT IN SMX 2 OUT IN SMX 3 OUT IN S...

Страница 11: ...you if you have taken the time to check available documentation It is also very helpful if you have serial numbers software revision numbers or other relavent information handy when you call If a har...

Страница 12: ...1C Are any files corrupted Yes Re install the program No If the problem cannot be resolved contact Crown Figure 8 Troubleshooting Flow Chart Does the software run PC Requirements Operating System Corr...

Страница 13: ...erface it is sometimes necessary to remove Pin 4 from the male connector on the standard RS232 cable Proceed to question 3C No Use the correct cable Question 3C Is the RS232 cable connected correctly...

Страница 14: ...ay not have any two components of the same type at the same address on the same loop and that addresses of 0 and 251 255 are not valid Question 4C Does the software have valid OIF and DLL files for th...

Страница 15: ...es the computer have a 16550 UART for the com port Yes Proceed to question 5B No Install a com port board with the 16550 UART chip This UART supports higher speeds and includes additional memory buffe...

Страница 16: ...lation or if the product has been repaired three or more times in the warranty period the most recent being at the Crown Factory Advanced replacements are only available through firms who have establi...

Страница 17: ...oftware in your hands A software upgrade is defined as an upgrade from one version level of software to a higher version level For example going from IQ For Windows 1 0 to version 1 1 would be an upgr...

Страница 18: ...ion problem is most likely between the computer and interface or on the Crown Bus 7 How does Break Detect work 8 List as many conditions as you can think of that would constitute a break in a Crown Bu...

Отзывы: