14
10) Vent connector must be inserted flush with inside face of the chimney liner and the space between vent connector and
chimney sealed tight. A thimble permanently cemented in place can be used to facilitate removal of vent connector for
cleaning.
11) Install the barometric draft regulator supplied with this boiler in accordance with the regulator manufacturer’s instructions.
No other draft regulator shall be used.
12) Secure all joints in the vent connector system with sheet metal screws. This includes the joint between the vent connector and
the boiler collar (see Figure 7.0, Detail ‘A’), as well as the barometric draft regulator. Use at least three screws at each joint.
FIGurE 7.0: tYPIcal VEnt SYStEM InStallatIOn anD cOMPOnEntS
taBlE 7.1: MInIMuM rEcOMMEnDED BrEEcHInG anD cHIMnEY SIZE
BOILER
MODEL
MINIMUM
BREECHING
DIA. (INCHES)
MINIMUM CHIMNEY REQUIREMENTS
ROUND I.D.
(IN.)
SQUARE. TILE
SIZE (NOMINAL) HEIGHT (FT.)
FSZ080
6
6
8 X 8
15
FSZ100
6
6
8 X 8
15
FSZ130
6
7
8 X 8
15
FSZ160
7
7
8 X 8
15
Содержание FSZ080
Страница 2: ......
Страница 14: ...12 FIGURE 6 4 ALLAIR FROM OUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM...
Страница 18: ...16 FIGURE 8 1 STEAM BOILER PIPING FOR GRAVITY RETURN...
Страница 26: ...24 FIGURE 10 2 TWO PIPE GRAVITY FEED SYSTEM NOT RECOMMENDED FIGURE 10 3 TWO PIPE LIFT SYSTEM...
Страница 29: ...27 FIGURE 11 0 WIRING CONNECTIONS DIAGRAM STEAM CG450 PROBE LWCO...
Страница 30: ...28 FIGURE 11 1 CONNECTIONS WIRING DIAGRAM FOR BURNER SPECIFIC PRIMARY CONTROL...
Страница 31: ...29 FIGURE 11 2 INDIRECT WATER HEATER FIELD WIRING...
Страница 41: ...39 Notes...
Страница 43: ...41...
Страница 45: ...43...
Страница 47: ...45...
Страница 51: ...Notes...