Crowcon Crowcon Gasmaster Скачать руководство пользователя страница 7

Crowcon Gasmaster 

Installation

3

Before commencing the installation and com-
misioning of your Gasmaster system, please read 
through the following information which will 
guide you through the whole process.

The installation instructions contained in this 
section are for a pre-configured 

Gasmaster

For instructions on installing and commissioning 
gas and fire detectors, please follow the user 
manual instructions supplied with the detectors. 
Alternatively contact Crowcon for advice.

To complete the installation of your Gasmaster 
system you will need to use the Operator panel 
and Menu. Full instructions can be found in sec-
tion 

III

. Operation, you are advised to familiarise 

yourself with the operator buttons on the front 
panel and the menu structure, see page 25. Some 
configuration steps may require you to enter 
Supervisor mode. Crowcon advises that personnel 
familiar with installing and commisioning gas and 
fire detection systems carry out this part.

If you have purchased a Gasmaster 1

Please follow the instructions in this section but 
ignore the reference to additional channels. 

If you have purchased a non-configured 
Gasmaster 4

Please follow the installation instructions for a 
pre-configured Gasmaster 4. Additional informa-
tion on setting-up your Gasmaster system can be 
found in section

 

III

Operation.

Step-by-step instructions

The installation and commissioning of your 
Gasmaster system is presented in easy to follow 
instructions. A summary table of contents detail-
ing a typical sequence of installation steps is 
shown below. Depending on your configuration 
some or part of each step may be omitted.

Note:

 two batteries are shipped separately from 

the main unit to prevent potential damage dur-
ing transit. These should be installed as shown 
in section 2.2.

2. Installation

Please read this first

Warning:

 Gasmaster is not certified for use 

in hazardous areas, but may be connected 
to detectors and/or alarm devices which are 
installed in a hazardous area. Instructions for 
field devices must be closely observed when 
installing a Gasmaster system.

2.1 Before installation 
2.2 General 
2.3 Mounting 
2.4 Cabling requirements 
2.5 Installing gas and fire detectors 
2.6 Installing output devices 
2.7 Connecting mains power 
2.8 Connecting input devices 
 

 2.8.1  Two wire 4-20mA devices 

 

 2.8.2  Three wire 4-20mA devices

 

 2.8.3  mV bridge pellistor detectors.

 

 2.8.4  Heat/smoke  detectors 

 

 2.8.5  Environmental Sampling Unit  
 (ESU) 

 

 2.8.6  Flame detectors  

 

 2.8.7  Remote inhibit and accept/ 
 

reset inputs 

2.9 Connecting output devices 
 

  2.9.1 Audible visual alarms 

 

  2.9.2 Common relay connections 

 

  2.9.3 Channel relay connections 

 

  2.9.4 Analogue outputs 

 

  2.9.5 RS485 communications 

2.10  Applying power 
2.11  Battery back-up time/ 

  power calculations 

2.12 Commissioning 
 

  2.12.1 Commissioning mV pellistor 

detectors

 

  2.12.2 Zero adjustment and calibration 

 

  2.12.3 Testing fire channels 

 

  2.12.4 Testing ESU channels 

Содержание Crowcon Gasmaster

Страница 1: ...Installation Operation and Maintenance Manual M070010 Issue 2 October 2014 Crowcon Gasmaster 1 to 4 channel gas detection control panel...

Страница 2: ...This product has been tested and found to comply with the European Directive 2004 108 EC and the EMC requirements of EN50270 It also complies with the Council Directive 2006 95 EC relating to electric...

Страница 3: ...ral 4 2 3 Mounting 5 2 4 Cabling requirements 5 2 5 Installing gas and fire detectors 6 2 6 Installing output devices 6 2 7 Connecting mains power 6 2 8 Connecting input devices 7 2 9 Connecting outpu...

Страница 4: ......

Страница 5: ...e channel display see figure 3 2 page 18 and a de populated terminal PCB All operating functions are identical to Gasmater 4 Gasmaster is designed for simple operation and all day to day functions can...

Страница 6: ...ER OUTPUT PARAMETERS BY BASEEFA OR ANY EC APPROVED CERTIFICATION BODY TO ANY SINGLE CHANNEL SHUNT ZENER DIODE SAFETY BARRIER WHICH IS ATEX CERTIFIED NOTE 7 TYPE XGARD CERTIFICATION No BASEEFA 04ATEX01...

Страница 7: ...e installation and commissioning of your Gasmaster system is presented in easy to follow instructions A summary table of contents detail ing a typical sequence of installation steps is shown below Dep...

Страница 8: ...splay PCB and batteries The terminal PCB contains the input modules and all of the input and output terminals The display PCB is con nected to the terminal PCB via a 50 way ribbon connector and is hin...

Страница 9: ...ovides a dimensional view of Gasmaster To access the mounting points first remove the front cover by unscrewing the fixings labelled in figure 2 1 Carefully remove the sounder connector from the displ...

Страница 10: ...aracteristics specified above There are a number of suitable ways of terminat ing cables and glands to Gasmaster dependant on the cable and gland type Steel wire armoured SWA cable and glands with ele...

Страница 11: ...se resistor Inputs can be gas detectors or flame detectors in 4 20 mA 2 wire sink or 3 wire sink or source configurations Gasmaster will track inputs from 3 to 21 5 mA at which point an over range fau...

Страница 12: ...owcon for specific wiring details for Crowcon detectors 2 8 1 Two wire 4 20mA devices Figure 2 6 shows a typical wiring configuration for a 2 wire current sink detector for safe area use only Figures...

Страница 13: ...ier 4 20mA Fire input module Set channel link to SINK see figure 2 5 and configuration to DET4 20 SINK see Menu System Overview section page 25 and 33 Refer to earth connection requirements on Figure...

Страница 14: ...SCR Channel Link Settings FIRE SINK SOURCE SIG FAN FAN Input 1 2 3 or 4 I S Link Settings Connections for ESU sampling device 4 20mA Fire input module 2 8 6 Flame detectors Figure 2 14 shows a typica...

Страница 15: ...o two general purpose A V alarm devices using xenon type beacons A greater number of LED based beacons may be powered contact Crowcon for advice Gasmaster is compatible with 12 V dc or 24 V dc A V ala...

Страница 16: ...n latching this is not configurable The Channel Alarm 2 and Common Alarm 2 relays can be configured as latching non latching or latch ing acceptable ESU Channels If the ESU sampling device slows signi...

Страница 17: ...ads must be removed if a remote RS 485 serial link is required Figure 2 19 485A 485B SCR J14 LK2 RS485 TERM Gasmaster RS 485 terminals 2 10 Applying power Before applying power ensure that any control...

Страница 18: ...ly recommended that persons intending to commission a Gasmaster system first read and understand the Operating instructions provided in section III Operation When all field devices have been connected...

Страница 19: ...f entering text strings 4 The Zero Wizard offers temporary Inhibit but you may wish to Inhibit all channels during the calibration process How to set global inhibit From the Supervisor menu scroll dow...

Страница 20: ...vates Each detector on a loop should be reset before testing the next to ensure that all detectors acti vate the alarm Heat detectors can be tested with a heat gun using the same method as described a...

Страница 21: ...isplay for one field device plus the message area Message display area In normal non alarm condition the message area displays the channel numbers and detector types e g CH4 refers to methane detector...

Страница 22: ...lash again if a new alarm is triggered Operator Panel Buttons Use the five operator buttons to respond to alarm conditions examine the status of system settings and configure Gasmaster ACCEPT RESET Pr...

Страница 23: ...ring Gasmaster installation or when Gasmaster is restarted Gasmaster will initialise the system by performing a self test The start up sequence is shown below Display and AV test GASMASTERII Software...

Страница 24: ...wizards Wizards are an extension of the menu system to guide the user through a process such as calibra tion A wizard menu will consist of selections user prompts and display status conditions during...

Страница 25: ...lphabet list To enter numbers or lower case characters continue press ing the Up or Down button For convenience after the first charac ter has been entered the next character will start from the same...

Страница 26: ...configurable and can be set as rising or falling Fire detectors Fire detectors in alarm will display FIRE in the channel display There is only one level of alarm for fire channels Note pressing the Ac...

Страница 27: ...t the fault LED will illuminate and the internal sounder will activate The message area will display FAULT and fault ID number The fault description will appear in the lower portion of the message are...

Страница 28: ...r operate Contact Crowcon Main supply fail Main supply has failed and the system 6 is running on batteries NVM hardware fail Fatal fault contact Crowcon 7 Loaded default settings System has returned t...

Страница 29: ...ocation Units Range Zero suppression Interpret 2 mA Stab time Fire reset time Alarm 1 Alarm 2 Note Menu items are hidden for unused channels Visible only for 4 20 mA Sink SRC Visible only for Fire con...

Страница 30: ...page 30 Detector 1 input low Detector input signal is between 1 and 3 mA 10 18 26 3 Only applies when the Interpret 2 mA command is set to Warning in the channel configuration Detector 1 initiated A 2...

Страница 31: ...ormally energised or de energised dependant on configuration No alarm means the relay is in its normal state In alarm means the relay is in its alarm or fault state 1 refers to the input channel use t...

Страница 32: ...er level 1 output becomes active for 3 seconds followed by Testing alarm L2 Sounder level 2 output becomes active for 3 seconds followed by Test complete Outputs de activate and display returns to the...

Страница 33: ...channel Inhibit Inhibit option will not be displayed if channels Values Inhibit on have already been set to inhibit using the menu Inhibit off shown above User confirmation Reminds the user to check t...

Страница 34: ...5 mA Forces common level 1 2 or Fault relays L1 Level 1 L2 Level 2 The values show the current state of each relay relays may be normally energised or de energised dependant on configuration No alarm...

Страница 35: ...ermines the operation of sounders connected to Values Latched the AV2 3 Drive terminals Non latched Latched means that in an alarm state the sounder Menu Item Values as shown on display Description Su...

Страница 36: ...ched Drive Fault drive Values De energised Energised Menu Item Values as shown on display Description Supervisor menu allows system tests to be performed and configurations to be changed A pass cont w...

Страница 37: ...9 Detector range e g 100 for a flammable detector Zero suppression ZFS Values Enabled Applies suppression to the first 3 of scale to Disabled prevent small deviations from zero being displayed If the...

Страница 38: ...ction 3 7 for details Press the Up and Down buttons to cycle through configuration for channels 2 3 4 Level at which the Level 1 relay will reset Allows hysteresis for applications such as ventilation...

Страница 39: ...n be inhibited individually or all at once The inhibit option is available in the Supervisor menu see section 3 6 on page 20 and the Menu System Overview on page 25 in the Operation chapter for detail...

Страница 40: ...eries should be checked regularly on units operating over 40 C Warning When replacing batteries care should be taken to ensure cables are re fitted as shown on the battery connection diagram Incorrect...

Страница 41: ...les simply plug in it is not necessary to remove power from the system providing the channel is set as Unused prior to insertion Once the module has been added the channel can be configured as appropr...

Страница 42: ...indication Integral 85 dB sounder EN 50270 EMC EN 61010 1 Low voltage directive ATEX EN60079 25 2010 Explosive atmospheres Intrinsically safe electri cal systems Gasmaster 4 288h x 278w x 110d mm 4 5...

Страница 43: ...10 S012304 Power supply assembly Complete with wiring looms S012205 Sounder assembly Complete with wiring loom M04683 Sounder seal M050067 Gasmaster 4 display label For front cover M050068 Gasmaster 1...

Страница 44: ...per case only single clicking or holding the Up button will advance forward through the avail able groups of characters A B C D X Y Z 0 1 2 7 8 9 A B C etc single clicking or holding the Down but ton...

Страница 45: ...mer Crowcon accept no liability for consequential or indi rect loss or damage howsoever arising including any loss or damage arising out of the use of the instru ment and all liability in respect of a...

Страница 46: ...Regional addresses Crowcon Gasmaster 42 Regional addresses...

Страница 47: ......

Страница 48: ......

Отзывы: