Crowcon Gasmaster
Menu system overview
33
Channels #1
Sets the input type for each channel, links on the
to #4
terminal PCB must also be set to the appropriate
positions (see section 2.8 for details).
Type
Values = Unused
No detector connected
DET 4-20 SRCE
4-20mA current source gas detector
DET 4-20 SINK
4-20mA current sink gas detector
FIRE 4-20 SRCE
4-20mA current source flame detector
Channels #
FIRE 4-20 SINK
4-20mA current sink flame detector
1 to #4 Cont.
FIRE CONV
Conventional smoke/heat or call points
ESU
ESU sampling device
PELLISTOR
mV Pellistor input modules and detectors only
Name
Detector name (e.g. CH4 for methane, O2 for
Values = 4 character string
oxygen, FIRE for smoke/heat detectors)
Location
Optional. Detector location or tag, will be shown
Values = 32 character string
on the message display if an alarm occurs
(e.g. Boiler Room).
Units*
Values = None
E.g. for an ESU channel
%LEL
For flammable channels
PPB
Very low range toxic gas detectors
PPM
General toxic gas detectors
%VOL
Oxygen or other high volume gases
FIRE
Flame or conventional smoke/heat detectors.
Range*
Values = 0 to 9999.9
Detector range (e.g. 100 for a flammable detector).
Zero suppression (ZFS)*
Values = Enabled
Applies suppression to the first 3% of scale to
Disabled
prevent small deviations from zero being displayed.
If the Level 1 alarm for a channel is set below 8%
of full scale, the level of suppression is reduced.
Interpret 2mA*
Values = Fault
Some gas detectors produce a 2 mA signal to
Warning
indicate a certain state.
Inhibit
This option determines how Gasmaster interprets
a signal between 1 and 3 mA.
Stab time
Inhibits the input for preset time after Gasmaster is
Values = 0 to 120 seconds
powered-up to prevent false alarms while the sensor
is
settling.
Fire reset time**
Time for which power is removed from smoke/heat
Values = 0 to 30 seconds
detectors when the Accept/Reset button is pressed.
Alarm L1 #1, #2, #3, #4
See submenu below
** Option will be shown for conventional fire channels only
Menu Item
Values
(as shown on display)
Description
Supervisor menu
(allows system tests to be performed, and configurations to be changed. A pass
cont.
word is required to enter this mode, see section 3.7 for details.)
*Options will
be shown for
4-20 mA input
channels only
*Options will
be shown for
4-20 mA input
channels only
Press the Up
and Down
Config Channel
#1 buttons to
cycle through
configuration
for channels #2,
#3 and #4.