Crowcon Crowcon Gasmaster Скачать руководство пользователя страница 17

Crowcon Gasmaster 

Installation

13

input signal. If the ‘pellistor saver’ function is 
enabled, at 95%LEL (this value is adjustable) gas 
concentration the channel will enter ‘pellistor 
saver’ mode (refer to section 3.9); the channel will 
go into fault and the analogue output signal will 
be set to 0mA.

If the ‘pellistor saver’ function is disabled the ana-
logue output will rise to a maximum of 25.8mA; 
the %LEL indication will depend on the gain levels 
set for the sensor.

Figure 2.18 

OUTPUT

1

SCR

0V

SIG

OUTPUT

2

SCR

0V

SIG

OUTPUT

3

SCR

0V

SIG

OUTPUT

4

SCR

0V

SIG

Link: 1-5V

No Link: 4-20mA

Link: 1-5V

No Link: 4-20mA

Link: 1-5V

No Link: 4-20mA

Link: 1-5V

No Link: 4-20mA

Gasmaster analogue output connection 

terminals

2.9.5.  RS-485 communications

Gasmaster can provide alarm and system informa-
tion to PLC/DCS/SCADA systems via a two-wire 
link using the Modbus RTU protocol (9600 baud, 
8 data bits, no parity, 1 or 2 stop bits). Up to 16 
Gasmaster systems can be 'multi-dropped' on 
a single two-wire link with a maximum cable 
length of 1 Km, two-core twisted pair cable is 
recommended. Single Gasmaster systems that 
are to communicate via the RS-485 link should 
have the 

RS485 TERM

 link made, which connects 

a terminating resistor. For multi-dropped systems 
the 

RS485 TERM

 link should be removed from all 

Gasmasters except the last unit on the line.

A Modbus specification document is available 
from Crowcon on request.

The RS-485 terminals on Gasmaster systems 
ordered with the optional local communications 
connector will be used for terminating the con-
nector leads. These leads must be removed if a 
remote RS-485 serial link is required.

Figure 2.19 

485A

485B

SCR

J

14

LK2

RS485
TERM

Gasmaster RS-485 terminals

2.10 

Applying power

Before applying power ensure that any 
control or shutdown systems to which the 
Gasmaster is connected are inhibited.

Once all field cables have been installed, the 
batteries can be connected as per the diagram 
attached to the chassis plate. (Refer to section 
4.4.) Gasmaster will not power up until an exter-
nal power supply is applied.

Apply power to Gasmaster from either the AC or 
24 V dc external supplies. Outputs are inhibited 
for a preset time after power-up, and the system 
will perform a start up sequence testing alarm 
indicators and the internal sounder. If after a set-
tling period faults are reported, check the sensor 
connections again or refer to "Faults menu (lists 
faults present on the system)" on page 24.

When power is applied the green Power LED will 
illuminate and flash every 5 seconds to indicate 
that the system is operational.

If the external supply fails, Gasmaster will con-
tinue to operate from its internal batteries and 
the Power LED will flash every second. Depending 
on configuration, Gasmaster will display either a 
Warning (Warning LED lights and the sounder will 
beep every 5 seconds) or a fault (the Fault LED 
and sounder will activate, and the fault relay will 
change state).

Gasmaster should display all channels being 
monitored. Allow sensors to settle before com-
mencing calibration, refer to sensor instructions 
supplied with detectors for recommended settling 
times.

Note:

 your Gasmaster is supplied pre-config-

ured, refer to the 

Specification and Inspection 

Certificate

 provided with your system. If no chan-

nels are configured, Gasmaster will display the 
following screen:

Содержание Crowcon Gasmaster

Страница 1: ...Installation Operation and Maintenance Manual M070010 Issue 2 October 2014 Crowcon Gasmaster 1 to 4 channel gas detection control panel...

Страница 2: ...This product has been tested and found to comply with the European Directive 2004 108 EC and the EMC requirements of EN50270 It also complies with the Council Directive 2006 95 EC relating to electric...

Страница 3: ...ral 4 2 3 Mounting 5 2 4 Cabling requirements 5 2 5 Installing gas and fire detectors 6 2 6 Installing output devices 6 2 7 Connecting mains power 6 2 8 Connecting input devices 7 2 9 Connecting outpu...

Страница 4: ......

Страница 5: ...e channel display see figure 3 2 page 18 and a de populated terminal PCB All operating functions are identical to Gasmater 4 Gasmaster is designed for simple operation and all day to day functions can...

Страница 6: ...ER OUTPUT PARAMETERS BY BASEEFA OR ANY EC APPROVED CERTIFICATION BODY TO ANY SINGLE CHANNEL SHUNT ZENER DIODE SAFETY BARRIER WHICH IS ATEX CERTIFIED NOTE 7 TYPE XGARD CERTIFICATION No BASEEFA 04ATEX01...

Страница 7: ...e installation and commissioning of your Gasmaster system is presented in easy to follow instructions A summary table of contents detail ing a typical sequence of installation steps is shown below Dep...

Страница 8: ...splay PCB and batteries The terminal PCB contains the input modules and all of the input and output terminals The display PCB is con nected to the terminal PCB via a 50 way ribbon connector and is hin...

Страница 9: ...ovides a dimensional view of Gasmaster To access the mounting points first remove the front cover by unscrewing the fixings labelled in figure 2 1 Carefully remove the sounder connector from the displ...

Страница 10: ...aracteristics specified above There are a number of suitable ways of terminat ing cables and glands to Gasmaster dependant on the cable and gland type Steel wire armoured SWA cable and glands with ele...

Страница 11: ...se resistor Inputs can be gas detectors or flame detectors in 4 20 mA 2 wire sink or 3 wire sink or source configurations Gasmaster will track inputs from 3 to 21 5 mA at which point an over range fau...

Страница 12: ...owcon for specific wiring details for Crowcon detectors 2 8 1 Two wire 4 20mA devices Figure 2 6 shows a typical wiring configuration for a 2 wire current sink detector for safe area use only Figures...

Страница 13: ...ier 4 20mA Fire input module Set channel link to SINK see figure 2 5 and configuration to DET4 20 SINK see Menu System Overview section page 25 and 33 Refer to earth connection requirements on Figure...

Страница 14: ...SCR Channel Link Settings FIRE SINK SOURCE SIG FAN FAN Input 1 2 3 or 4 I S Link Settings Connections for ESU sampling device 4 20mA Fire input module 2 8 6 Flame detectors Figure 2 14 shows a typica...

Страница 15: ...o two general purpose A V alarm devices using xenon type beacons A greater number of LED based beacons may be powered contact Crowcon for advice Gasmaster is compatible with 12 V dc or 24 V dc A V ala...

Страница 16: ...n latching this is not configurable The Channel Alarm 2 and Common Alarm 2 relays can be configured as latching non latching or latch ing acceptable ESU Channels If the ESU sampling device slows signi...

Страница 17: ...ads must be removed if a remote RS 485 serial link is required Figure 2 19 485A 485B SCR J14 LK2 RS485 TERM Gasmaster RS 485 terminals 2 10 Applying power Before applying power ensure that any control...

Страница 18: ...ly recommended that persons intending to commission a Gasmaster system first read and understand the Operating instructions provided in section III Operation When all field devices have been connected...

Страница 19: ...f entering text strings 4 The Zero Wizard offers temporary Inhibit but you may wish to Inhibit all channels during the calibration process How to set global inhibit From the Supervisor menu scroll dow...

Страница 20: ...vates Each detector on a loop should be reset before testing the next to ensure that all detectors acti vate the alarm Heat detectors can be tested with a heat gun using the same method as described a...

Страница 21: ...isplay for one field device plus the message area Message display area In normal non alarm condition the message area displays the channel numbers and detector types e g CH4 refers to methane detector...

Страница 22: ...lash again if a new alarm is triggered Operator Panel Buttons Use the five operator buttons to respond to alarm conditions examine the status of system settings and configure Gasmaster ACCEPT RESET Pr...

Страница 23: ...ring Gasmaster installation or when Gasmaster is restarted Gasmaster will initialise the system by performing a self test The start up sequence is shown below Display and AV test GASMASTERII Software...

Страница 24: ...wizards Wizards are an extension of the menu system to guide the user through a process such as calibra tion A wizard menu will consist of selections user prompts and display status conditions during...

Страница 25: ...lphabet list To enter numbers or lower case characters continue press ing the Up or Down button For convenience after the first charac ter has been entered the next character will start from the same...

Страница 26: ...configurable and can be set as rising or falling Fire detectors Fire detectors in alarm will display FIRE in the channel display There is only one level of alarm for fire channels Note pressing the Ac...

Страница 27: ...t the fault LED will illuminate and the internal sounder will activate The message area will display FAULT and fault ID number The fault description will appear in the lower portion of the message are...

Страница 28: ...r operate Contact Crowcon Main supply fail Main supply has failed and the system 6 is running on batteries NVM hardware fail Fatal fault contact Crowcon 7 Loaded default settings System has returned t...

Страница 29: ...ocation Units Range Zero suppression Interpret 2 mA Stab time Fire reset time Alarm 1 Alarm 2 Note Menu items are hidden for unused channels Visible only for 4 20 mA Sink SRC Visible only for Fire con...

Страница 30: ...page 30 Detector 1 input low Detector input signal is between 1 and 3 mA 10 18 26 3 Only applies when the Interpret 2 mA command is set to Warning in the channel configuration Detector 1 initiated A 2...

Страница 31: ...ormally energised or de energised dependant on configuration No alarm means the relay is in its normal state In alarm means the relay is in its alarm or fault state 1 refers to the input channel use t...

Страница 32: ...er level 1 output becomes active for 3 seconds followed by Testing alarm L2 Sounder level 2 output becomes active for 3 seconds followed by Test complete Outputs de activate and display returns to the...

Страница 33: ...channel Inhibit Inhibit option will not be displayed if channels Values Inhibit on have already been set to inhibit using the menu Inhibit off shown above User confirmation Reminds the user to check t...

Страница 34: ...5 mA Forces common level 1 2 or Fault relays L1 Level 1 L2 Level 2 The values show the current state of each relay relays may be normally energised or de energised dependant on configuration No alarm...

Страница 35: ...ermines the operation of sounders connected to Values Latched the AV2 3 Drive terminals Non latched Latched means that in an alarm state the sounder Menu Item Values as shown on display Description Su...

Страница 36: ...ched Drive Fault drive Values De energised Energised Menu Item Values as shown on display Description Supervisor menu allows system tests to be performed and configurations to be changed A pass cont w...

Страница 37: ...9 Detector range e g 100 for a flammable detector Zero suppression ZFS Values Enabled Applies suppression to the first 3 of scale to Disabled prevent small deviations from zero being displayed If the...

Страница 38: ...ction 3 7 for details Press the Up and Down buttons to cycle through configuration for channels 2 3 4 Level at which the Level 1 relay will reset Allows hysteresis for applications such as ventilation...

Страница 39: ...n be inhibited individually or all at once The inhibit option is available in the Supervisor menu see section 3 6 on page 20 and the Menu System Overview on page 25 in the Operation chapter for detail...

Страница 40: ...eries should be checked regularly on units operating over 40 C Warning When replacing batteries care should be taken to ensure cables are re fitted as shown on the battery connection diagram Incorrect...

Страница 41: ...les simply plug in it is not necessary to remove power from the system providing the channel is set as Unused prior to insertion Once the module has been added the channel can be configured as appropr...

Страница 42: ...indication Integral 85 dB sounder EN 50270 EMC EN 61010 1 Low voltage directive ATEX EN60079 25 2010 Explosive atmospheres Intrinsically safe electri cal systems Gasmaster 4 288h x 278w x 110d mm 4 5...

Страница 43: ...10 S012304 Power supply assembly Complete with wiring looms S012205 Sounder assembly Complete with wiring loom M04683 Sounder seal M050067 Gasmaster 4 display label For front cover M050068 Gasmaster 1...

Страница 44: ...per case only single clicking or holding the Up button will advance forward through the avail able groups of characters A B C D X Y Z 0 1 2 7 8 9 A B C etc single clicking or holding the Down but ton...

Страница 45: ...mer Crowcon accept no liability for consequential or indi rect loss or damage howsoever arising including any loss or damage arising out of the use of the instru ment and all liability in respect of a...

Страница 46: ...Regional addresses Crowcon Gasmaster 42 Regional addresses...

Страница 47: ......

Страница 48: ......

Отзывы: