5. DIAGNOSTICS AND TROUBLESHOOTING 

 

5.1. Mechanical Failures 

 

Error 

 

Cause 

 

Remedy

 

Significant temperature rise

 

Overload 
Holding brake not released 

Reduce the load 
Check control of the holding brake 

Whistling or knocking

 

Faulty bearings

 

Contact the after-sales service

 

Friction noise

 

A rotary transmission device is catching

 

Align the transmission device

 

Radial vibration

 

Transmission device incorrectly aligned 
Transmission device unbalanced 
Twisted shaft 
Resonance in the fixing

 

Align the transmission device 
Balance the transmission device 
Contact the after-sales service 
Check the rigidity of the motor fixing

 

Axial vibration

 

Transmission device incorrectly aligned 
Transmission device being knocked 
Resonance in the fixing

 

Align the transmission device 
Check the transmission device 
Check the rigidity of the motor fixing

 

 
 
 

5.2. Electrical Failures 

 

Error 

 

Cause 

 

Remedy

 

The motor does not start or 
starts with difficulty

 

Overload 
Fault in the connection wires 

 

Reduce the load 
Check the connection wires  
Contact the after-sales service 

Significant temperature rise in 
the stator

 

Overload

 

Reduce the load

 

Temperature rise in the 
connection terminals 

Power supply wires disconnected or 
loose

 

Tighten the screws

 

 
 

 

Содержание SMI21 80140301

Страница 1: ...his manual in a safe place Give this manual and any other documents relating to the product to anyone that uses the product Read and be sure to comply with all the safety instructions and the section...

Страница 2: ...3 Installation 8 3 1 Overview of the Installation Procedure 10 3 2 Electromagnetic Compatibility EMC 10 3 3 Prior to Mounting 11 3 4 Mounting the Motor 12 3 5 Electrical Installation 13 3 6 Connectin...

Страница 3: ...al safety instructions are identified by warning symbols Depending on how serious the situation is the safety instructions are split into 3 risk categories DANGER DANGER indicates a directly dangerous...

Страница 4: ...the mechanical electrical and electronic equipment in the whole installation 1 2 Use in Compliance with Industry Practice As demonstrated in these instructions this product is a component designed for...

Страница 5: ...tage on the power cable and check that it is less than 12 VDC Install protective covers and ensure they are closed before energization Failure to comply with these precautions will result in death or...

Страница 6: ...0 April 27th 2018 1 4 Standards and concepts The product is ROHS and REACH confirmed following European Directive 2011 65 CE Following this confirmation the product is CE marked The electrical design...

Страница 7: ...Never exceed the maximum axial and radial forces Protect the shaft from any impact When press fitting components do not exceed the maximum permissible axial force Failure to comply with these precaut...

Страница 8: ...ds These can cause sensitive equipment to fail Keep people with implants such as pacemakers away from the motor Do not place sensitive equipment in the immediate vicinity of the motor Failure to compl...

Страница 9: ...or is not designed to carry loads If subjected to stress the motor can be damaged or even fall Do not use the motor as a step Prevent the motor from being used in any way other than its intended purpo...

Страница 10: ...that the motor power supply leads must be kept separate from line supplies or cables carrying signals Comply with the following measures as concerns EMC Measures relating to EMC Effect Keep the cables...

Страница 11: ...cleaning product used Flange mounting surface The mounting surface must be stable flat and clean In regards to installation make sure that all dimensions and tolerances are respected Specification of...

Страница 12: ...rces leads to rapid bearing wear a broken shaft or damage to the internal encoder Never exceed the maximum axial and radial forces Protect the shaft from any impact When press fitting components do no...

Страница 13: ...tor itself or devices placed on the same power supply DANGER ELECTRIC SHOCK High voltages can appear unexpectedly on the motor connection The motor produces a voltage when the shaft turns Protect the...

Страница 14: ...erheating due to an electric arc Failure to comply with these precautions can result in injury or damage to equipment CAUTION IRREPARABLE PRODUCT DAMAGE CAUSED BY REVERSED POLARITY Incorrect connectio...

Страница 15: ...on Make sure this cannot cause any damage Do not continue with the test if there is anybody or any obstacle in the danger zone Failure to comply with these precautions can result in death serious inju...

Страница 16: ...he holding brake is fully released Make sure that the holding brake is fully released before initiating a movement WARNING UNEXPECTED MOVEMENT As a result of incorrect wiring or other error the drives...

Страница 17: ...for heat dissipation Check the temperature when performing a test Failure to comply with these precautions can result in injury or damage to equipment CAUTION VOLTAGE SURGES During braking phases the...

Страница 18: ...fixing Align the transmission device Balance the transmission device Contact the after sales service Check the rigidity of the motor fixing Axial vibration Transmission device incorrectly aligned Tra...

Страница 19: ...ind out what steps to take We recommend that the following operations are done at regular intervals Connections and fixing Check the connection cables and connections regularly for signs of damage Rep...

Страница 20: ...e holding torque indicated on the technical data sheet If the holding torque is markedly different from the stated values turn the motor shaft by hand 25 turns in both directions Repeat the operation...

Отзывы: