Alarm settings for GEM detectors are voltage settings. The range of 0 - 4.0 VDC is equal to the
full measurement range of the sensor. E.g. HVAC CO sensor has a standard measurement range
of 0-200 ppm. Therefore, 4.0 VDC = 200 ppm. Reference the formula below and the table in
Section
7.5 Jumpers
.
DESIRED SET POINT / SENSOR RANGE = % OF RANGE
e.g. 100 ppm / 200 ppm = 50% of range
50% OF 4.0 VDC = 2.0 VDC.
Therefore the required voltage setting to achieve an alarm set point of 100 ppm is 2.0 VDC.
7.6.1 Voltage Reference Table for Alarm Settings
SENSOR / GAS MEASUREMENT RANGE
LOW ALARM
SET VOLTAGE
HIGH ALARM
SET VOLTAGE
CO
0 - 200 ppm
25 ppm / 0.50 VDC
100 ppm / 2.00 VDC
CO
0 - 200 ppm
35 ppm / 0.70 VDC
200 ppm / 4.00 VDC
NO
2
0 - 10 ppm
0.7 ppm / 0.28 VDC
1.0 ppm / 0.40 VDC
NO
2
0 - 10 ppm
2.0 ppm / 0.8 VDC
5.0 ppm / 2.00 VDC
O
2
0 - 25.0% Volume
19.5% Vol. / 3.12 VDC
23.0% Vole. / 3.68 VDC
O
2
0 - 25.0% Volume
17.0% Vol. / 2.72 VDC
18.5% Vol. / 2.96 VDC
O
3
0 - 2.00 ppm
0.10 ppm / 0.20 VDC
0.30 ppm / 0.60 VDC
O
3
0 - 2.00 ppm
0.30 ppm / 0.60 VDC
1.00 ppm / 2.00 VDC
NO
0 - 100 ppm
25 ppm / 1.00 VDC
50 ppm / 2.00 VDC
H
2
S
0 - 50 ppm
10 ppm / 0.80 VDC
15 ppm / 1.20 VDC
SO
2
0 - 20 ppm
2 ppm / 0.40 VDC
5 ppm / 1.00 VDC
H
2
0 - 4,000 ppm
1000 ppm / 1.00 VDC
2000 ppm / 2.00 VDC
C
3
H
8
0 - 50% LEL
10% LEL / 0.80 VDC
20% LEL / 1.60 VDC
C
3
H
8
0 - 50% LEL
20% LEL / 1.60 VDC
40% LEL / 3.20 VDC
CH
4
0 - 50% LEL
10% LEL / 0.80 VDC
20% LEL / 1.60 VDC
CH
4
0 - 50% LEL
20% LEL / 1.60 VDC
40% LEL / 3.20 VDC
H
2
0 - 50% LEL
10% LEL / 0.80 VDC
20% LEL / 1.60 VDC
Freons
(R series)
0-2000 ppm
500 ppm / 1.00 VDC
1000 ppm / 2.00 VDC