cGas Detector Digital Transmitter - Installation Manual
Rev. A | 2020.03
The Comm Type should be BACnet. Press the UP button until you see Instance
ID.
Comm Type
BACnet
Instance ID
270100
Press ENTER. Use the UP button to enter the numeric value. Move to the next
digit by pressing EN
TER. When fi nished, press ENTER to confi rm and Exit.
Instance ID
>0270111
Confirm?
>270111
N
>Y
8.3.3 Change BACnet® Baud Rate
All devices on the same BACnet® network must have the same baud rate. The
default BACnet® baud rate is 76,800.
From the main display, press ENTER.
Enter passcode 1001 using the UP button and ENTER button.
Enter Password
1001
Press ENTER to access the Basic Menu.
Basic Menu
Press Enter
The Comm Type should be BACnet. Press the UP button until you see Comm
Baud.
Comm Type
BACnet
Comm Baud
>19200
Press ENTER. Using the UP or DOWN buttons, scroll through the baud rates to
choose from:
• 9,600
• 14,400
• 19,200