cGas Detector Digital Transmitter - Installation Manual
Rev. A | 2020.03
• Temperature
• Humidity
Press the UP button to fi nd Test Reading. To make a change, press ENTER and
then use the UP, DOWN and ENTER buttons to enter the value.
Test Reading
0 PPM NO2
Test Reading
>10.0 PPM NO2
Press ENTER and then again to Confi rm Y.
Confirm?
>10.0 PPM NO2
N
>Y
Test Reading
10.0 PPM NO2
The test will start as soon as you press ENTER to confi rm and will remain in
the test mode as long as the Test Reading screen remains untouched.
To stop
the test, press the UP or DOWN button. Test another reading value or press
ENTER to Exit.
7.6.2 Test Relay (models with Option -RLY installed)
NOTE:
Before testing the relay, notify the appropriate people so unnecessary
distress or response is not caused by activating fans or equipment or
inadvertantly calling the fi re department or other emergency response team.
From the main display, press ENTER.
Enter passcode 0001 using the UP button and ENTER button.
Enter Password
0001
Press ENTER to access the Test Menu.
Test Menu
Press Enter
In the Test Relay menu, the default entry is Untripped. Press ENTER and use the
UP button to change to Tripped. Press ENTER. You will hear a soft click and the
relay will activate accordingly, respecting its failsafe setting and ON/OFF delays.