34
© 2020 All rights reserved. Data subject to change without notice.
cGas Detector Digital Transmitter - Installation Manual
Rev. A | 2020.03
on the confi guration of the transmitter. The warm-up period takes between 2
and 5 minutes depending on the gas sensors type.
NOTE:
The cGas Detector will be visible on the controller / BAS / DDC system
during the warm-up countdown but a correct reading will not show up until the
unit has fi nished the warm-up period and the sensor(s) has stabilized.
All alarms will be disabled during the system warm-up period. After the
warm-up period, the system may exhibit gas alarm condition(s) if one or
both of the sensors has not completely stabilized during the warm up period.
This is normal and the length of time the gas alarms exist is dependent upon
the length of time since the unit was last powered up, and the state of the
environment it is installed in. Refer to
Section 6.1 Special Considerations for
Different Types of Sensors
for more information about sensor warm up time.
Upon power-up, all sensors* should be left to warm up for 24 hours prior to
considering the gas readings to be accurate.
*except, Ammonia, which should be left to warm up for 48 hours.
All sensors are calibrated in the factory prior to shipping and should not
require calibration at the time of a routine installation or replacement.
7.2 Navigating the Menu Structure
The three programming push-buttons inside the enclosure are used to navigate
through the cGas Detector menu structure. Refer to
Section 5.1 Exterior
Enclosure
for location photo.
ENTER begins a process or moves you to the next screen in the same menu.