![Critical Environment Technologies cGas Detector Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/critical-environment-technologies/cgas-detector/cgas-detector_installation-manual_2686176041.webp)
© 2020 All rights reserved. Data subject to change without notice.
41
Rev. A | 2020.03
cGas Detector Digital Transmitter - Installation Manual
Test Relay:SB
Untripped
Test Relay:SB
>Tripped
To stop the relay test, Press ENTER and the UP button to change to Untripped.
Press ENTER. You will hear a soft click and the relay will deactivate.
Test Relay:SB
>Untripped
When fi nished, press ENTER and then UP to Exit.
8 MODBUS & BACNET CONFIGURATION
The cGas Detector can be changed from Modbus® to BACnet® or vice versa
in the fi eld.
8.1 Changing Digital Communication Type in the Field
When the communication type is changed from/to Modbus® or BACnet®, the
device will reset. This will briefl y interrupt communications on the network it is
connected to.
From the main display, press ENTER.
Enter passcode 1001 using the UP button and ENTER button.
Enter Password
1001
Press ENTER to access the Basic Menu.
Basic Menu
Press Enter
Comm Type
MODBUS
Press ENTER. Use the UP or DOWN buttons to choose MODBUS or BACNET or
Cancel. Press ENTER. If you have changed the communication type, the device
will display Reset Device.