cGas Detector Analog Transmitter - Installation Manual
Calibrate Menu
Press Enter
In the Selected Channel menu, if Temperature (or Humidity) is not displayed,
press ENTER and use the UP button to scroll to find the item you are looking for.
Press ENTER.
Selected Channel
CO2
Selected Channel
>Temperature
Selected Channel
>Humidity
Use the UP button to find Temperature Adj (or Humidity Adj). If you want to
change the offset value, press ENTER. Change the offset value using the UP or
DOWN and ENTER buttons.
Temperature Adj
>-4.0 degC
Humidity Adj
>+02 %RH
Press ENTER to confirm the value is correct. If you entered the wrong value,
press the UP button to move the cursor to N and press ENTER and reenter the
value.
Confirm?
>-4.0 degC
N
>Y
Confirm?
>+2 %RH
N
>Y
7.8 Test Functions
7.8.1 Test Analog Output
Testing the analog output allows you to determine if the installation was
successful. The test forces the cGas Detector to output a predetermined signal
to the controller or DDC/BAS to test that the correct signal is being transmitted
and the controller responds as configured (ie. if analog output is configured for
VFD control, the fans operate as expected).
From the main display, press ENTER.
Enter passcode 0001 using the UP button and ENTER button.