cGas Detector Analog Transmitter - Installation Manual
Rev. B | 2021.08
In the Selected Channel menu, if Temperature is not displayed, press ENTER
and use the UP button to scroll to find Temperature. Press ENTER.
Selected Channel
CO2
Selected Channel
>Temperature
Use the UP button to find Temperature Unit. If you want to change the unit type,
press ENTER.
Temperature Unit
Celsius
Press the UP button to choose Fahrenheit press ENTER and ENTER to exit.
Temperature Unit
>Fahrenheit
7.7 Temperature and/or Relative Humidity Offset
NOTE:
This menu item only applies if the cGas Detector has the -RHT option
installed.
NOTE:
Depending on the configuration, the device will show the temperature
in either Celsius or Fahrenheit. The units can be changed at any time, refer to
Section
7.6 Change Units (
o
C or
o
F) of Temperature Readings
.
The temperature and relative humidity sensor is calibrated prior to shipping.
If the readings on the cGas Detector are higher or lower than another device
measuring the ambient temperature or relative humidity, you can adjust
the reading by setting an offset value so the reading is more accurate. The
Temperature offset value is a number of degrees in either direction of 0 and the
Humidity offset value is a percentage between 0 or 100.
From the main display, press ENTER.
Enter passcode 3032 using the UP button and ENTER button.
Enter Password
3032
Press ENTER to access the Calibrate Menu.