3.2.4. Cable linking the earth to the installation
The charger's case should be connected to the installation's earthing system in accordance with current standards
governing the relevant application.
To that effect, connect the installation-to-earth cable to the earthing screw located inside the charger (see chapter
“user interface area”).
This cable's cross-section should be at least 2.5mm², type HO7-VK and equipped with an appropriate terminal.
3.2.5. Precautions regarding electromagnetic disturbance generated by the appliance
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the
receiving ends.
Keep cable length and shielding connections down to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should be
flattened against conductive parts).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any branch-offor short-out intended to power another
appliance are prohibited.
(*) This is a recommendation for installation rather than an obligation.
The installing electrician should decide whether or not to use shielded cable
depending on the EMC environment.
3.2.6. Cabling principle
3.2.6.1. Cabling type
3.2.6.2. Other type of installation
Refer to appendix 6.