The generator highlighted in blue and whose connection icon is closed corresponds to the controller (and
therefore to the generator) that you are supervising. To switch the
i4Gen
connection to another controller,
press the corresponding controller
connection icon.
To be able to use this function, the configuration of the controllers has to respect the following conditions
·
The controllers must be configured in the same subnet : the first 3 numbers of their IP addresses must
be the same (ex : 192.168.11.X).
·
The generator number (v2001) must be different for each controller
·
The 4th number of the IP address of a controller must correspond to its generator number (ex: GE
number = 2, IP address = X.X.X.2)
Example of configuration with 3 controllers
·
Controller 1
o
Number of GE=1
o
IP address
= 192.168.11.
1
·
Controller 2
o
Number of GE=2
o
IP address
= 192.168.11.
2
·
Controller 3
o
Number of GE=3
o
IP address
= 192.168.11.
3
In this way, in the "
power-plant
" page, GE1 will correspond to controller 1 (192.168.11.1), GE2 will
correspond to controller 2 (192.168.11.2) and GE3 will correspond to controller 3 (192.168.11.3).
Note: If the configuration does not meet the above conditions, the connection switching may not work
properly.
Password expiration
This parameter is used to activate/deactivate the password level expiration.
Expiration delay
If the password expiration has been enabled, this parameter is used to configure the delay after which the
password will expire.