3)  If a higher pump differential is needed, grip the cord
 

near the neck of the fl oat, then using the other hand, 

 

exert a steady force on the lower edge of the cable 

 

clamp. The cable clamp should slide up to the new 

 

pivot point. Attach the level control to the discharge 

 

hose in the manner described above.

4)  Plug the level control plug into the receptacle, then 
 

plug the pump into the piggyback plug. One cycle of 

 

operation should be observed , so that any potential 

 

problems can  be corrected.

5)  It is recommended that the fl oat should be set to insure
 

that the sump well liquid level never drops below the 

 

top of the motor housing or a minimum level of  6 

 

inches above the pump bottom.

6.)  Figure 3 shows a typical connection for pumps with the
 wide 

angle 

fl oat and piggy-back plug, for manual and

 automatic 

operations.

Automatic-  

Plug fl oat cord into outlet, then plug pump

 cord 

into 

fl oat cord.

Manual-  

Plug pump cord directly into outlet.

C-4) Electrical Connections:

WARNING ! - Pump must be used in a circuit 
protected by a ground fault interrupter.

WARNING ! - All model pumps and control 
panels must be properly grounded per THE 
NATIONAL ELECTRIC CODE or CANADIAN 
ELECTRIC CODE and STATE, PROVINCE and 
LOCAL electric codes.  Improper grounding 
voids warranty.

C-4.1) Power Cable:

The cord assembly mounted to the pump must not be 
modifi ed in any way except for shortening to a specifi c 
application. Any splice between the pump and the control 
panel must be made in accordance with the electric codes. 
It is recommended that a junction box, if used, be mounted 
outside the sump or be of at least NEMA 4 (EEMAC-4) 
construction if located within the wet well. Do not use the 
power cable to lift pump.  

NOTE: THE WHITE WIRE IS 

NOT A NEUTRAL OR GROUND LEAD, BUT A POWER 
CARRYING CONDUCTOR.

C-4.2) Overload Protection:

Single Phase - The type of in-winding overload protector 
used is referred to as an inherent overheating protector 
and operates on the combined effect of temperature and 
current.

 This means that the overload protector will trip out and 
shut the pump off if the windings become too hot, or the 
load current passing through them becomes too high. It 
will then automatically reset and start the pump up after 
the motor cools to a safe temperature. In the event of an 
overload, the source of this condition should be deter-
mined and rectifi ed immediately.

DO NOT LET THE PUMP CYCLE OR RUN IF AN OVER-
LOAD CONDITION OCCURS !

If current through the temperature sensor exceeds the 
values listed, an intermediate control circuit relay must 
be used to reduce the current or the sensor will not work 
properly.

TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous

Amperes

Inrush

Amperes

110-120

3.00

30.0

C-4.3) Wire Size: 

Consult a qualifi ed electrician for proper wire size. See 
table for electrical information.

FIGURE 3

Manual

Automatic

FIGURE 2

Содержание Barnes SE411HT

Страница 1: ...stant product improvement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 107027A Rev D Series SE411HT 4Hp 1750 RPM 60 Hz Manual Index ...

Страница 2: ...NS 3 A PUMP SPECIFICATIONS 4 B GENERAL INFORMATION 5 C INSTALLATION INSTRUCTIONS 5 6 D START UP OPERATION 7 E PREVENTATIVE MAINTENANCE 7 F SERVICE AND REPAIR 7 10 G REPLACEMENT PARTS 10 TROUBLE SHOOTING 11 CROSS SECTION Fig 10 12 PARTS LIST 13 RETURN GOODS POLICY 15 WARRANTY START UP REPORT WARRANTY REGISTRATION SPECIAL TOOLS and EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT s...

Страница 3: ...ings DO NOT insert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed...

Страница 4: ...nless Steel PAINT Air Dry Enamel SEAL Design Single Mechanical Reservoir Secondary Exclusion Seal Material Carbon Ceramic Buna N Hardware 300 Series Stainless CORD ENTRY 15 ft 5m Cord with plug On 115 volt and Stainless Wire Mesh Strain Relief Pressure Gromment for sealing and strain relief SPEED 1750 RPM nominal UPPER BEARING Single Row Ball Oil Lubricated LOWER BEARING Single Row Ball Oil Lubric...

Страница 5: ...nes representative or Crane Pumps Systems Inc Service Department in Piqua Ohio telephone 937 778 8947 or Crane Pumps Systems Canada Inc Bramton Ontario 905 457 6223 SECTION C INSTALLATION C 1 Location These pumping units are self contained and are recommended for use in a sump or basin The sump or basin shall be vented in accordance with local plumbing codes This pump is designed to pump effluent ...

Страница 6: ...t be modified in any way except for shortening to a specific application Any splice between the pump and the control panel must be made in accordance with the electric codes It is recommended that a junction box if used be mounted outside the sump or be of at least NEMA 4 EEMAC 4 construction if located within the wet well Do not use the power cable to lift pump NOTE THE WHITE WIRE IS NOT A NEUTRA...

Страница 7: ...nd allowing the pump to operate through it s pumping cycle The time needed to empty the system or pump down time should be recorded on the start up sheet SECTION E PREVENTATIVE MAINTENANCE As the motor is oil filled no lubrication or other maintenance is required and generally Barnes pumps will give very reliable service and can be expected to operate for years on normal sewage pumping without fai...

Страница 8: ...on around the sealed areas and inspect joints for air bubbles If after five minutes the pressure is still holding constant and no bubbles are observed slowly bleed the pressure and remove the gauge assembly Replace the pipe plug using a sealant If the pressure does not hold then the leak must be located CAUTION Pressure builds up extremely fast increase pressure by TAPPING air nozzle Too much pres...

Страница 9: ...ate 2 and tighten motor screws Install o ring 11 onto seal plate 2 Slide the gland nut friction rings and grommet onto cord set see Figure 5 and slip cord through motor housing 12 Connect motor wires per Figure 6 Place motor housing 12 squarely onto seal plate while pulling excess cord through hole Tighten socket head screws 13 into motor housing Slide the friction rings 8b grommet 8c and gland nu...

Страница 10: ... serial number and date code Paragraph G 4 2 Pump model number Paragraph G 3 3 Pump part number Paragraph G 2 4 Part description 5 Item part number 6 Quantity required 7 Shipping instructions 8 Billing Instructions G 2 PART NUMBER The part number consists of a six 6 digit number which appears in the catalog A one or two letter suffix may follow this number to designate the design configuration Thi...

Страница 11: ...eller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as...

Страница 12: ...12 FIGURE 10 ...

Страница 13: ... 2 051449 Friction Ring 8c 1 051451 Grommet 8d 1 108335A Wire Mesh Cord Grip 304 Stainless 8e 1 108336 Hex Nut 1 2 Stainless 10 1 016660 Self Tapping Screw 8 32 x 3 8 lg Stainless 11 1 019289 O Ring 12 1 093065A Motor Housing 13 2 084948 Socket Hd Cap Screw 1 4 20 x 1 25 Stainless 14 1 068053 Exclusion Seal 15 1 112561TE Impeller Cast Iron 16 1 099295 Ground Wire 17 1 068984 Gasket 18 1 089120A Vo...

Страница 14: ...formance specifications must be in writing and such writing must be signed by our authorized representative Due to inaccuracies in field testing if a conflict arises between the results of field testing conducted by or for user and laboratory tests corrected for field performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND EVALUATI...

Страница 15: ...nt To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pumps...

Страница 16: ...Notes ...

Отзывы: