5.2.4 Multi-Function Outputs
The SV200 drive is equipped 4 Multi-Function Outputs. One is a Normally Open
contact between AX1 and AX2 on the control board. The other three are Open
Collector 24 VDC outputs at Q1, Q2, and Q3, see Fig. 5.2.4.
AUX Output [SER: Code No.10]: AUX Output
(Factory Default: FST_HI)
Q1 Output
[SER: Code No. 11]: Q1 Output
(Factory Default: FST_LO)
Q2 Output
[SER: Code No. 12]: Q2 Output
(Factory Default: FDT_HI)
Q3 Output
[SER: Code No. 13]: Q3 Output
(Factory Default: OL)
Range: FST_LO
(See Section 5.2.12)
FST_HI
(See Section 5.2.12)
FDT_HI
(See Section 5.3.20)
FDT_PULSE
(See Section 5.3.20)
FDT_BAND
(See Section 5.3.20)
OL
(See Section 5.3.10)
LV
RUN
LOW VOLTAGE SIGNAL
Multi-Function Output terminals AX1 and AX2 programmed to LV will close when the
DC Link voltage falls below the low voltage level of the drive (200VDC for 230 VAC,
and 400VDC for 460 VAC drives).
Fig. 5.2.3: Under-voltage Fault Signal
RUN / STOP SIGNAL
The Multi-Function Output terminals AX1 and AX2 programmed to RUN will close
when the drive changes from a stop condition to a run condition.
B3, B4
DC link voltage
time
ON
230V
200V
AX1, AX2
QI
EXTG
Open Collector Output
(24VDC, 50mA)
OL
24V DC
Supply
Relay
+
Fig. 5.2.4: Open Collector Multi-function Output