10
Electrical Specifications by Heater Input
Item #
kW
Max Amps
Required Breaker
Req. Wire Size
18kW
18
75
2 x 40A Double Pole
2 x 8/2 AWG with Ground
24kW
24
100
3 x 40A Double Pole
3 x 8/2 AWG with Ground
29kW
28.8
120
3 x 40A Double Pole
3 x 8/2 AWG with Ground
Power Rates
Item #
240V
220V
208V
18kW
18,000 Watts
15,125 Watts
13,520 Watts
24kW
24,000 Watts
20,166 Watts
18,026 Watts
29kW
28,800 Watts
24,200 Watts
21,632 Watts
Your tankless water heater is now installed and ready to use! Follow the General Operating Instructions to complete the setup.
Terminal Block in Unit
40 Amp
Double Pole
40 Amp
Double Pole
40 Amp
Double Pole
40 Amp
Double Pole
40 Amp
Double Pole
Unit Requires 10 AWG ground wire - one for each 240V circuit
Unit Requires 10 AWG ground wire - one for each 240V circuit
L1
L1
L2
8/2 AWG
8/2 AWG
L2
240V
240V
L1 L2
L1 L2
L1
L1
L1
L2
8/2 AWG
8/2 AWG
8/2 AWG
L2
L2
240V
240V
240V
L1 L2
L1 L2
L1 L2
Wiring Diagram for 18kW
Wiring Diagram for 24kW, 29kW