11
Electrical Specifications by Heater Input
Item #
kW
Max Amps
Required Breaker
Req. Wire Size
36kW
36
150
4 x 40A Double Pole
4 x 8/2 AWG with Ground
Power Rates
Item #
240V
220V
208V
36kW
36,000 Watts
30,250 Watts
27,040 Watts
Your tankless water heater is now installed and ready to use! Follow the General Operating Instructions to complete the setup.
40 Amp
Double Pole
40 Amp
Double Pole
40 Amp
Double Pole
40 Amp
Double Pole
Unit Requires 10 AWG ground wire - one for each 240V circuit
L1
L1
L1
L2
8/2 AWG
8/2 AWG
8/2 AWG
L2
L2
240V
240V
240V
L1 L2
L1 L2
L1 L2
L1
L2
240V
L1 L2
8/2 AWG
Your tankless water heater is now installed and ready to use! Follow the General Operating Instructions to complete the setup.
Terminal Block in Unit
Wiring Diagram for 36kW