Trouble-shooting

Page 13

Operation & Maintenance Manual - Vision Chilled Displays

3.0 - BUILD UP OF ICE ON THE COIL

In conditions of high humidity it is possible for ice to accumulate on the coil, and not be fully cleared by the defrost system. 
This problem is usually only likely to occur on units operating 24hours a day in conditions of high humidity. The result will be 

a failure to maintain temperature, as airflow through the coil is restricted. 

If during cleaning an excessive build up of ice is observed, turn the unit off overnight with the main deck and airflow baffle 

plates removed. 

Isolate the display unit completely from the mains electricity supply. Turning off the power switch on the display 

is not sufficient.

If the build up was very heavy and the unit is fitted with an automatic evaporating drip tray it will be necessary 

to guide the water resulting from the melting of the ice into a bucket rather than the evaporating drip tray oth-

erwise it will overflow. 

Remove the evaporator drip tray and locate a funnel or bucket under the plastic waste pipe located above it. 
See cleaning instructions for removal of the drip tray. 

When all the ice has melted re-assemble the tank and deck components, re-fit the evaporator drip tray, then switch the 

power back on and check the operation of the unit.

If you are in any doubts of your ability to carry out the above procedure please contact our service department for assis-
tance.

Please note that a visit by a service engineer to clear the coil of ice will not be covered by warranty 
unless it is established that it was caused by a component failure.

If the build up repeats itself try turning the unit off every night.

If this does not solve the problem call our service department on 0151 548 2211 to check the operation of the 
defrost system.  

Содержание vision aire

Страница 1: ...n range Counterline Limited Randles Road Knowsley Business Park Merseyside L34 9HZ United Kingdom tel 44 0 151 548 2211 fax 44 0 151 549 2179 service enquiries servicelog counterline co uk spare parts enquiries spareparts counterline co uk general enquiries enquiries counterline co uk web www counterline co uk ...

Страница 2: ...justment 1 8 Installation Of Wall Sited Chilled Vision Displays 2 CLEANING 2 0 Cleaning Safety Note 2 1 Stainless Steel 2 2 Sliding Rear Doors 2 3 Vision Glass 2 4 Rear Air Guides 2 5 Cleaning Chilled Display Main Tank 2 6 Condensing Unit Finned Coil 2 7 Automatic Evaporating Drip Tray 3 TROUBLE SHOOTING 3 0 Ice Build Up On The Coil 3 1 Self Help Guide Page 3 Page 3 Page 4 Page 4 Page 5 Page 5 Pag...

Страница 3: ... or points be installed below the evaporator tray area as water may overflow and cause a hazard Vision display units are heavy We strongly recommend the use of mechanical lifting equipment when handling the units and positioning them in counters If no such lifting equipment is available then sufficient personnel must be available to handle each unit without contravening Company or site Health and ...

Страница 4: ...the unit serial number to hand before calling Vision units are available as stand alone units with an integral base or as a drop in unit with under slung compressor The basic operation and maintenance of these units is the same 1 0 SWITCHING YOUR VISION CHILLED DISPLAY UNIT ON Info Set point button Manual defrost decrease button Manual activation increase button Stand by button INDICATIONS CONTROL...

Страница 5: ...oller will be pre set at the factory to give a food display temperature of 2 5 C in typical operating condi tions Under normal conditions the controller displays the actual temperature of the cold air around the food If you need to alter the pre set temperature proceed as follows Gantry digital controller See diagram below 1 Press Button for a least half a second to display the set point value 2 B...

Страница 6: ...y glasses whilst removing any glass If your display is fitted with a full height sneeze screen you will need to remove it before attempting to carry out this operation Refer to the section on replacement glass for instructions You will also need to remove the glass shelves Firstly using both hands lift off each glass shelf and set aside on a surface protected by a soft cloth Do not lay one shelf o...

Страница 7: ...her with fixings inside the O M manuals These stops must be fitted by the person installing the display The wall stops must not be removed under any circumstances as they create the necessary space through which the ex haust hot air from the compressor unit will escape None fitting or removal of the wall stops will invalidate the product warranty and any subsequent service calls maybe chargeable I...

Страница 8: ...g Replacement of the doors is the reverse of the above procedure Take hold of the door in both hands as you did for removal ensuring that the edge with the two rollers is at the bottom Offer the top edge of the door into the top track and gently push it up as far as it will go Move the lower edge of the door away from you until the rollers are over the track and then lower it back into position Ch...

Страница 9: ... using a damp cloth and detergent Finally spray the interior of the tank and the finned cooling coil generously with a sanitising solution such as Dettox Avoid using excess water if your unit is not connected to a plumbed drain as this may cause the automatic evaporating drip tray to overflow Re assembly is the reverse of the above When cleaning the unit you must inspect the main cooling coil You ...

Страница 10: ... remove the glass shelves see instructions 1 11 pg 12 to gain access to the air guides In units with rear doors access is obtained by simply opening the doors At weekly intervals these should be removed by lifting upwards and away from the doors or framework and then wiped on both sides with a soft damp cloth Under no circumstances should any abrasive be used as it will scratch the surface of the ...

Страница 11: ... the wiring the coil cover plate can then be removed and the main cooling coil exposed Remove any food debris using a vacuum cleaner followed by a cloth and detergent Wipe the fan blades using a damp cloth and detergent Finally spray the interior of the tank and the finned cooling coil generously with a sanitising solution such as Dettox Avoid using excess water if your unit is not connected to a ...

Страница 12: ...ut 400 mm square and comprises a grid of very fine black metal fins These fins become choked with dust and airborne particles They should be cleaned using a soft brush to loosen the dust and a vacuum cleaner to remove it The fins are very deli cate and considerable care is required If you are in any doubt as to your ability to carry out this operation safely call your installer and arrange for the...

Страница 13: ...0mm high resting in it is a heating element which is connected via a short lead to a plug Remove the plug from its socket and carefully lift out the drip tray and element together There is likely to be some water in the tray which you should discard Inside the tray and on the element will be a build up of deposits similar to the scale inside a kettle As much of this as possible must be removed by ...

Страница 14: ...ting drip tray it will be necessary to guide the water resulting from the melting of the ice into a bucket rather than the evaporating drip tray oth erwise it will overflow Remove the evaporator drip tray and locate a funnel or bucket under the plastic waste pipe located above it See cleaning instructions for removal of the drip tray When all the ice has melted re assemble the tank and deck compon...

Страница 15: ...iciency of the display Steam is seen from louvered door The automatic condensate waste tray is operating normally The temperature of the produce is too high Check setting of temperature controller Ensure airways are not blocked Ensure fans are operating Ensure the doors are closed Move display case from draughts air conditioning vents The condensing unit coil maybe blocked See section 2 6 page 12 ...

Отзывы: