Shown below the notes about installation clearance of a unit.
1
Installation clearance at above and below the unit.
Please have clearance of at least 25mm above and below the
unit to avoid heat accumulation.
2
Installation clearance at the side of the unit.
Please have clearance of at least 15mm side the unit to avoid
interfering with heat radiation from housing. However, refer to
Table 4.1, if adjacent device of the unit (including power supply) is
a heat source.
1
Convection
Convection
2
25mm
or more
1
25mm
or more
Fig.4.3 Installation clearance
Table 4.1 Installation clearance at the side of the unit.
No.
Model
Adjacent device of the unit
Non-heat source Heat source(
*
)
1 KLEA120F, KLNA120F
15mm or more 25mm or more
2 KLEA240F, KLNA240F
15mm or more 25mm or more
*
Reference value when same power units are adjacent.
4.2 Derating curve depend on input voltage
¡
Derating curve depend on input voltage.
Derating curve depend on input voltage is shown in Fig.4.4.
[AC V]
85
100
80
100
Load Factor
[%]
Fig.4.4 Derating curve depend on input voltage
4.3 Derating curve depend on ambient temperature
¡
The operative ambient temperature as different by input voltage.
Derating curve is shown below.
¡
In the hatched area,the specification of Ripple,Ripple Noise is dif-
ferent from other area.
¡
Derating Curve (Convection)
¿
KLEA120F, KLNA120F
60
40
0
100
80
10
30
20
-30
0
60 70 80
20 30 40 45
25
65
50
-20 -10
(A)
(B)
(C)
(D), (E)
Ambient Temperature [
C
]
Load factor [%]
Vin=AC85V - 170V
*
*
Derating curve depend on input voltage is required.
Fig.4.5 Derating curve depend on ambient temperature
0
100
8
70
0
30
20
60
40
(A)
(B)
(C)
(D), (E)
55
Ambient Temperature [
C
]
Load factor [%]
Vin=AC170V
-
264V
0
10
-30
60 70 80
20 30 40 45
65
50
-20 -10
Fig.4.6 Derating curve depend on ambient temperature
¿
KLEA240F, KLNA240F
60
40
100
80
20
0
(A)
(B)
(C)
(D), (E)
*
Ambient Temperature [
C
]
Load factor [%]
Vin=AC85V - 170V
15
0
10
-30
60 70 80
20 30 40 45
65
50
-20 -10
*
Derating curve depend on input voltage is required.
Fig.4.7 Derating curve depend on ambient temperature
0
100
80
20
60
40
(A)
(B)
(C)
(D), (E)
35
25
Ambient Temperature [
C
]
Load factor [%
]
Vin=AC170V
-
264V
55
0
10
-30
60 70 80
20 30 40
65
50
-20 -10
Fig.4.8 Derating curve depend on ambient temperature
AC-DC Power Supplies DIN Rail Type
Instruction Manual
KL-11