Shown below the notes about installation clearance of a unit.

1

 Installation clearance at above and below the unit. 

    Please have clearance of at least 25mm above and below the 

unit to avoid heat accumulation.

2

 Installation clearance at the side of the unit.

    Please have clearance of at least 15mm side the unit to avoid 

interfering with heat radiation from housing.  However, refer to 
Table 4.1, if adjacent device of the unit (including power supply) is 
a heat source.

1

Convection

Convection

2

25mm 

or more

1

25mm 

or more

Fig.4.3  Installation clearance

Table 4.1  Installation clearance at the side of the unit.

No.

Model

Adjacent device of the unit

Non-heat source Heat source(

*

)

1 KLEA120F, KLNA120F

15mm or more 25mm or more

2 KLEA240F, KLNA240F

15mm or more 25mm or more

*

Reference value when same power units are adjacent.

4.2 Derating curve depend on input voltage

¡

Derating curve depend on input voltage.

  Derating curve depend on input voltage  is shown in Fig.4.4.

[AC V]

85

100

80

100

Load Factor 

[%]

Fig.4.4  Derating curve depend on input voltage 

4.3 Derating curve depend on ambient temperature

¡

The operative ambient temperature as different by input voltage. 
Derating curve is shown below.

¡

In the hatched area,the specification of Ripple,Ripple Noise is dif-
ferent from other area.

¡

Derating Curve (Convection)

¿ 

KLEA120F, KLNA120F

60

40

0

100

80

10

30

20

-30

0

60 70 80

20 30 40 45

25

65

50

-20 -10

(A)

(B)

(C)

(D), (E)

Ambient Temperature [

C

]

Load factor [%]

Vin=AC85V - 170V

*

*

 Derating curve depend on input voltage is required.

Fig.4.5  Derating curve depend on ambient temperature

0

100

8

70

0

30

20

60

40

(A)

(B)

(C)

(D), (E)

55

Ambient Temperature [

C

]

Load factor [%]

Vin=AC170V

 - 

264V

0

10

-30

60 70 80

20 30 40 45

65

50

-20 -10

Fig.4.6  Derating curve depend on ambient temperature

¿ 

KLEA240F, KLNA240F

60

40

100

80

20

0

(A)

(B)

(C)

(D), (E)

*

Ambient Temperature [

C

]

Load factor [%]

Vin=AC85V - 170V

15

0

10

-30

60 70 80

20 30 40 45

65

50

-20 -10

*

 Derating curve depend on input voltage is required.

Fig.4.7  Derating curve depend on ambient temperature

0

100

80

20

60

40

(A)

(B)

(C)

(D), (E)

35

25

Ambient Temperature [

C

]

Load factor [%

]

Vin=AC170V

 - 

264V

55

0

10

-30

60 70 80

20 30 40

65

50

-20 -10

Fig.4.8  Derating curve depend on ambient temperature

AC-DC Power Supplies DIN Rail Type

Instruction Manual

KL-11

KL-11

Содержание KLEA120F

Страница 1: ...t method Switching frequency KLz Input current A 1 Rated input fuse Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series opera...

Страница 2: ...allation Method KL 10 KL 9 KL 9 KL 9 KL 9 KL 9 KL 9 KL 9 KL 9 3 1 Series Operation 3 2 Parallel Operation 4 1 Installation Mounting methods 4 2 Derating curve depend on input voltage 4 3 Derating curv...

Страница 3: ...40F KLNA120F Terminal Number Terminal Name Function 1 PE Protective earth Terminal 2 AC N Input Terminals 3 AC L 4 VOUT Output Terminals 5 VOUT Output Terminals 6 DC_OK LED for output voltage confirma...

Страница 4: ...LNA240F When the overcurrent protection circuit is activated and the output voltage drops to a certain extent the output becomes hiccup so that the average current will also decrease 2 Functions 2 4 O...

Страница 5: ...balance between the values of I1 and I2 Please make sure that the value of l3 does not exceed the rated current of a power supply l3 rated current value 4 Assembling and Installation Method 4 1 Insta...

Страница 6: ...ve depend on input voltage 4 3 Derating curve depend on ambient temperature The operative ambient temperature as different by input voltage Derating curve is shown below In the hatched area the specif...

Страница 7: ...ambient temperature year Life Expectancy Load factor Io 75 Load factor 75 Io 100 A Convection AC85 170V Ta 40C or less 10years or more 6years Ta 50C 5years 3years AC170 264V Ta 45C or less 9years 6ye...

Страница 8: ...5C or less 5years 5years Ta 15C 5years 5years AC170 264V Ta 25C or less 5years 5years Ta 35C 5years 3years D and E Convection AC85 170V Ta 0C or less 5years 5years Ta 10C 5years 2years AC170 264V Ta 1...

Отзывы: