4.12 Auxiliary power (AUX)
¡
The unit has the auxiliary power (AUX: 5V1A) in CN1 to provide
for the remote ON/OFF and external circuits.
¡
When the Global inhibit function activates, the following derating
for the AUX is required.
Derating for AUX: Io(AUX)
[
0.5A
¡
The AUX circuit(AUX, AUXG) is isolated from the input, the output,
the FG, and other function terminals except GI1.
¡
If the output current of the AUX exceed 1A, the unit might be dam-
aged or malfunction.
When the DC-DC converter is connected to the AUX, the cur-
rent might be severalfold of the normal current when starting up.
Please check the current.
¡
The maximum external capacitor to the AUX is 47μF.
4.13 Medical Isolation grade
¡
AME series meets 2MOPP
1MOPP
Safety GND
primary secondary
2MOPP
Fig.4.7 Medical Isolation Grade
5 Assembling and
Installation Method
5.1 Installation method
¡
The unit has cooling fans.
Ensure that the inlet and outlet vents are not blocked.
Output
module
Air flow
FA
N
Fig.5.1 Air flow
¡
Fig.5.2 is the recommended installation method when the unit is
mounted by screws. When the unit is installed by any other meth-
od, please take into account of its weight and secure it.
A
B
C
Top
Top
Top
CN1
CN1
CN1
Fig.5.2 Installation method 1
¡
Avoid installation method 2 as shown in Fig.5.3, which can cause
stress on the mounting holes.
¡
Maximum length of mounting screws is 6mm (Refer to Fig.5.4).
NO
CN1
TOP
Chassis of
customer system
Screw M4
Chassis of
AME series
6mm max
Fig.5.3 Installation method 2
Fig.5.4 Mounting screw
5.2 Output side attaching externally capacitor
¡
If the external capacitor is too large, the power supply might not
start up.
Table 5.1 Connectable External capacitor on the output side [μF]
module code
capacitance
A
0 to 47,000
B
0 to 18,000
C
0 to 12,000
D
0 to 2,200
AC-DC Power Supplies Configurable Type
Instruction Manual
AME-14