CT1001/CT1002 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer Setup
Name
Settings
Notes
Initial
Setting
Record
Cycles per hour (cph)
for 1st Stage
Conventional Heat
1- 1 cph used for steam and gravity.
3-3 cph used for hot water system and high
efficiency (90% or better) furnaces.
5-5 cph used for standard fossil fuel forced air (less
than 80% efficient) systems (factory setting)
9-9 cph used for electric furnaces.
2, 4, 6, 7, 8, 10, 11, 12other cycle rate settings.
Not shown if system
selection is heat pump.
Selection in this stage
changes default cph for 2nd
stage heat.
Cycles per hour (cph)
for 2nd Stage Heat
(Aux Heat for 2H/1C
Heat Pumps)
1-1 cph used for steam and gravity.
3-3 cph for hot water systems and high efficiency
(90% or better) furnaces.
5-5 cph for standard fossil fuel forced air (less than
90% efficient) systems (factory setting).
9-9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems.
2, 4, 6, 7, 8, 10, 11, 12other cycle rate settings.
Only shown if two stages of
heat are selected.
Cycles per hour (cph)
for 3rd Stage Heat
Aux Heat for 3H/2C
(Heat Pumps)
1-1 cph used for steam and gravity.
3-3 cph for hot water systems and high efficiency
(90% or better) furnaces.
5-5 cph for standard fossil fuel forced air (less than
90% efficient) systems (factory setting).
9-9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems.
2, 4, 6, 7, 8, 10, 11, 12-other cycle rate settings.
Only shown if 3H/2C heat
pump is selected.