Alarms
If the machine detects a fault, corresponding information appears in a pop-up window. Additionally,
a warning symbol appears in the standard view's upper right corner, as long as one or more problems
remain.
The following alarms can appear. Recommended corrective action is also given for each alarm.
Alarms
Action/advice
On or more slaves not responding
This alarm appears when the machine is used as master in
a network that has lost contact with one or more of its
slave machines. If this alarm appears, check all system
cables and the power supply to all machines. When
communication has been re-established the alarm
disappears automatically again.
Ambient temperature too high!
The machine has switched off all heaters due to too high
ambient temperature (above 40 degrees Celsius). If
continuous fan is selected, the fan continues to run. The
machine resumes operation automatically if the
temperature drops.
Ambient temperature too low
The machine resumes operation automatically if the
temperature rises. Check the function of the extra heater.
No contact with internal control board Internal fault. If the alarm remains, contact a service
technician.
Internal sensor fault Temp and RH
sensor
Internal fault. If the alarm appears after the machine has
been disassembled, the fault may be because the sensor
connection to the cover has not been installed correctly. If
not, and if the alarm remains, contact a service technician.
External Temp and RF sensor fault
The machine has lost contact with the external temp and
RH sensor(s). Check that the cables are correctly installed.
When contact with the external sensors has been lost, the
machine automatically returns to using the built-in temp
and RF sensor.
The statistics cannot be saved to the
memory
Internal fault. If the alarm remains, contact a service
technician.
The event log cannot be saved to the
memory
Internal fault. If the alarm remains, contact a service
technician.
Humidity too low
The machine resumes operation automatically if the
humidity rises.
Hot gas sensor fault
Internal fault. If the alarm remains, contact a service
technician.
Solenoid fault
Internal fault. If the alarm remains, contact a service
technician. The machine switches to stop defrosting.
Stop defrosting takes longer than
expected
Internal fault. If the alarm remains, contact a service
technician.