Triton R134a Range
Manual operation undercounter cooler
Triton R134a Range
Page 25
Cornelius Deutschland GmbH
Document no: TD1014600EN
Version A, 24.09.2019, Index 0
11 Adjusting / Position of the Icebank Probe
(To be done only by « operator »)
12 Installation Check List
You can use this check list to review the installation of the device. Fill out the check list and keep it with the
operating instructions.
Part number of the device:
__________________
Serial number of the device:
__________________
Installation site:
__________________
Installation date:
__________________
Installed by:
__________________
Settings:
Target
Actual
Water flow pressure:
0.2 MPa (2 bar, dynamic)
____ MPa
CO
2
-pressure:
0.52 to 0.58 MPa (5.2 to 5.8 bar)
____ MPa
CO
2
-volume at 4°C:
4.0% by vol.
____ % by vol.
Carbonator filling time:
about 8 sec
____ sec
CO
2
-pressure switch
0.3 MPa (3 bar)
____ MPa
Stillwater pressure switch
0.32 MPa (3.2 bar)
____ MPa switch
stillwatercontrol
0.42 MPa (4.2 bar)
____ MPa