CH550 and CH551 Chiller Operator’s & Installation Manual

© 2002-2010, IMI Cornelius Inc.

- 1 -

Publication Number: 91272

INTRODUCTION

The Cornelius “CH” Series Water Chillers (Models CH550-A and CH551-A) are specifically designed to cool 
clean water before it is circulated to the cooling application. The Unit includes a complete refrigeration system 
and associated controls housed in a sturdy sheet metal enclosure with perforated panels for air circulation. 
Options include a reservoir and a choice of pumps and temperature controls to provide a self-contained liquid 
cooling circulation system tailored to a particular closed loop or tank application.

On closed loop systems, the Unit is provided with a pump and reservoir for recirculation of water from the chiller 
to the process. On tank cooling systems, the Unit is provided without the reservoir and the pump is optional for 
recirculation of water from the chiller to the tank. Control temperature is sensed on the outlet of the chiller for 
closed loop systems and it is sensed on the inlet of the chiller for tank cooling systems.

The pump options consist of a small magnetic drive pump as standard with a variety of magnetic drive and 
positive displacement pumps available for particular flow and pressure requirements. An optional bypass valve is 
available for the pump circulation system. (This valve is standard on Units utilizing the positive displacement 
pumps). This can be used to adjust pump flow and pressure to match process requirements. This valve also 
allows internal recirculation within the chiller in the event the chiller outlet is obstructed.

SPECIFICATIONS

CH550-A

CH551-A

Condensing Unit Horse Power

1/2

1/2

Electrical (Volts/Phase/Hz)

115/1/60

230/1/60

F. L. A. (Amps)

12.5

6.2

Reservoir Capacity (Gal.)

2

2

Refrigerant 134-A (Lbs)

1.375

1.375

Stainless Steel Connections

1/2 in. FPT

1/2 in. FPT

Operating Water Temperature Range

40°-100° F

40°-100° F

Net Weight (Lbs)

160

160

Dimensions : Depth (Inches)

Width (Inches)

Height (Inches)

16-3/4

15-1/8

28-1/2

16-3/4

15-1/8

28-1/2

Содержание CH 551

Страница 1: ...550 AND CH551 Operator s Installation Manual Release Date August 9 2002 Publication Number 91272 Revision Date May 10 2010 Revision D Visit the IMI Cornelius web site at www cornelius com for all your...

Страница 2: ...n trained and are skilled in working with electrical plumbing pneumatic and mechanical equipment It is assumed that appropriate safety precautions are taken and that all local safety and construction...

Страница 3: ...tart Up Operation 2 Thermostat 2 Temperature Controller 2 Standard Thermostat Eliwell IC902 3 Maintenance 3 Service 3 Removing Wrapper 3 Replacing Swtich 3 Replacing Thermostat 4 Replacing Fan Blade a...

Страница 4: ......

Страница 5: ...r to the tank Control temperature is sensed on the outlet of the chiller for closed loop systems and it is sensed on the inlet of the chiller for tank cooling systems The pump options consist of a sma...

Страница 6: ...ans of conduit from the junction box in the rear of the chiller cabinet to a properly fused disconnect of proper amperage or 2 Wired to a properly rated power cord and plugged into an outlet with appr...

Страница 7: ...hen it is not being used 3 Always ensure that all air inlets and outlets are free of obstructions MAINTENANCE The chiller requires very little normal maintenance The condenser fins should be cleaned b...

Страница 8: ...ving Wrapper 2 Remove the screws securing the fan guard to the fan shroud 3 Remove the conduit connection at the back of the motor and disconnect the wire leads 4 Remove the bolts securing the fan mou...

Страница 9: ...ble De Ionized Water 1 5 Meg ohms Acceptable De Ionized Water 5 Meg ohms Acceptable with Stainless Steel PVC only No Copper or Brass Propylene Glycol Lab Industrial Grade Acceptable 30 Glycol 70 Water...

Страница 10: ...ne to or from chiller is restricted B Low water level C Inoperable pump A Inspect lines and remove any obstructions B Ensure that tank is full C Check for obstruction or binding impeller replace pump...

Страница 11: ...hermostat Eliwell No EWPC902 3 620603708 Blade Fan 4 620603711 Motor Fan CH550 115V 620603709 Motor Fan CH551 230V 5 Condenser 6 Not Used 7 620603701 Compressor CH550 115V 620603702 Compressor CH551 2...

Страница 12: ...hat all equipment and parts are free from defects in material and workmanship under normal use and service For a copy of the warranty applicable to your Cornelius or Wilshire product in your country p...

Страница 13: ......

Страница 14: ...IMI Cornelius Inc www cornelius com...

Отзывы: