Low Voltage Load Wiring
Each channel can be individually configured to support any of
the following low voltage load control standards: 0-10V, DSI
or broadcast
DALI (DSI and DALI - Canada and Mexico Only).
The high voltage sections for each channel continue to provide
switched hot outputs to power the controlled loads.
ote:
N
Support for multiple low voltage load control
standards may not be permissible in certain
countries. In such cases, the required control
standard must be stated when ordering.
The low voltage load wiring circuits are located just below the
control panel, accessible either through a removable mini panel
or when the complete casing is removed.
Connections are made easy by using removable plug blocks
which snap into terminals mounted on the circuit boards shown
below:
signal
sign
al
signal
sign
al
1
7
13
19
2
8
14
20
3
9
15
21
4
10
16
22
5
11
17
23
6
12
18
24
0V
0V
0V
0V
signal
sign
al
signal
sign
al
0V
0V
0V
0V
signal
sign
al
signal
sign
al
0V
0V
0V
0V
signal
sign
al
signal
sign
al
0V
0V
0V
0V
signal
sign
al
signal
sign
al
0V
0V
0V
0V
signal
sign
al
sign
al
sign
al
0V
0V
0V
0V
For each circuit, the low voltage control protocol to be used is
selected using the configuration menu on the control panel.
The programming of the Source Controller channels is covered
within the accompanying System Manual.
ote:
N
DALI signals for each channel are output in broadcast
mode only - it is not possible to individually address mul-
tiple DALI luminaires on the same control wire.
The low voltage load control circuits are PELV (Protected Extra
Low Voltage).
Low Voltage Load Wiring Flows
The casing provides four knockouts on the base panel for use
by exiting low voltage load cables as well as control wiring.
Each knockout is 0.89 inches (22.5 mm) in diameter.
Use appropriate conduits and couplers to link with raceways or
cable runs, as necessary.
IMPORTANT: Low voltage load wiring should be installed with a
suitable separation to parallel high voltage cables, according to
local and national codes.
Indicators
An indicator is assigned to each low voltage output channel
to provide quick visual feedback. In each case, the indicator
(located next to the output connectors) will mimic the dimmed
status of the associated channel, from zero to full brightness.
Indicators
Universal Source Controller
WaveLinx Wired
MN503104ML
page 12