![Cooper S225-10-30 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/cooper/s225-10-30/s225-10-30_installation-operation-and-maintanance-instructions_2661569044.webp)
VR-32 Voltage Regulator Installation, Operation, and Maintenance Instructions
44
Applied Voltage
.
Apply a source voltage of 120 V (*240 V international)
to the control panel external source terminals. Check
the polarity of the source leads before connecting to
the control external source terminals.
*International units setup for 240 V may have a 240 V
decal at the control panel external source terminals.
A .
Apply the hot lead to the Black terminal on the
external source.
B .
Ground to White terminal.
Note:
Failure to connect properly will cause damage
to control.
2 .
Switch the
Internal/ External
switch to
External
.
3 .
Switch the
Auto/Remote-Off-Manual
switch to
Manual
.
4 .
Using the
Raise/Lower
switch, lower the tap-changer
until the position indicator reads
6 lower
.
5
. Switch the
Auto/Remote-Off-Manual
switch to
OFF
.
6 .
Switch the
Internal/External
Switch to
OFF
.
7 .
Remove the external source from the external source
terminals.
8 .
Using at least a #14 stranded copper cable, jumper the
“S”, “L” and “SL” bushing terminal together.
.
Connect the applied ac voltage potential test lead from
the high voltage test transformer to one of the bushing
terminals.
0 .
Ground the tank of the of the voltage regulator.
.
Close the
C
knife switch and open all other knife
switches, which are located on the back panel inside
the control box.
TAbLE 8
Applied Potential for New Units
BIL
Applied AC Potential Test Voltage (kV)
30
10
45
15
60
19
75
26
95
34
125
40
150
50
200
70
TAbLE 9
Applied Potential for Used Units
(Units that have been energized on a system)
BIL
Applied AC Potential Test Voltage (kV)
30
6
45
9
60
11.5
75
15.5
95
20.5
125
24
150
30
200
42
2 .
Refer to the regulator nameplate for the BIL and refer
to Table 8 or 9 to determine the correct ac potential
voltage. Starting at zero volts, increase the voltage to
the specified level, within 15 seconds.
3 .
The potential voltage is to be applied for 60 seconds.
The following may indicate a failure:
A .
A sudden increase in test circuit current.
B .
An indication of smoke and bubbles.
C .
An audible sound such as a thump.
D .
An appreciable increase in partial discharge (coro-
na) level.
4 .
Once a failure has been detected, use extreme caution
when doing any diagnostic testing.
5 .
Once the applied voltage test time has been completed
and there is no signs of problem lower the potential
voltage to zero volts.
6 .
Return the tap-changer back to neutral by using an
external source voltage to the control and by using the
Internal/External
switch,
Auto/Remote-Off-Manual
switch and the
Raise/Lower
switch.
7 .
Remove the potential lead and jumper from the bush-
ings and disconnect the ground from the tank.
DANGER:
High Voltage. This is a high-voltage
test. The high-voltage potentials can arc to a per-
son or to equipment over a short distance. The regula-
tor must be in a test cage or similar protective device.
Failure to comply will result in serious injury or death.
VR-T230.0
CAUTION:
Equipment Damage. Be mindful of polar-
ity when using an external source. Polarity reversal will
result in control damage.
VR-T201.0
CAUTION:
Equipment Damage. Only an ac power sup-
ply is to be used to energize the control externally. Do
not use a dc-to-ac voltage inverter. Failure to comply can
cause excessive harmonics to be generated and result in
damage to the front panel.
VR-T204.1
WARNING:
Hazardous Voltage. The regulator
tank must be solidly earth grounded. Failure to
comply can cause severe personal injury and equipment
damage.
VR-T225.0