This interlacing of the two coils reduces the interwinding
leakage reactance to a very low value. The reactor is com-
pletely isolated from ground by stand-off insulators since
the reactor coil is at line voltage above ground. The reactor
core, core clamps, and other associated parts approach
this level.
The current transformer is a toroid, through which the
load current passes. It furnishes a current proportional to
load current for the line-drop compensator and metering
features.
The tap-changer enables the regulator to provide regula-
tion in smooth, accurately proportioned steps at a con-
trolled speed that minimizes arcing and extends contact
life. Figures 26 and 27 (see Appendix) illustrate the typical
internal wiring schemes. Most of the wiring is on the tap-
changer itself. The terminal board inside the junction box
on the cover connects the internal tank wiring to the posi-
tion indicator and control. The junction box wiring is shown
in Figure 28 (see Appendix).
7
S225-10-30
!
SAFETY
FOR LIFE
Figure 15 .
Power circuit — series transformer (similar characteristics to Type A) .
S
SL
L
N
1
2
3
4
5
6
7
8
G
G
V
1
C
2
C
1
E
1
E
2
E
3
JBB-G
JBB-S
2
C
O
N
T
R
O
L
Source
VL
VR
Source
Bushing
Shunt
Transformer
Series
Transformer
Reactor
Equalizer Winding
Source-Load
Bushing
Polarity
Marker
JBB-C
2
JBB-C
1
Load Bushing
Current Transformer
Load
Potential
Transformer
Load
Reversing
Switch
Figure 14
.
Power circuit — series winding located on the load-side (ANSI Type A) .
S
SL
L
Reactor
Equalizer Winding
Series Winding
Reversing
Switch
Polarity
Marker
Current
Transformer
Load Bushing
N
1 2 3 4 5 6 7 8
VR
VL
Source-Load
Bushing
Shunt
Winding
G
G
V
1
C
2
C
1
E
1
E
2
E
3
JBB-G
JBB-S
2
JBB-C
2
JBB-C
1
Control
Load
Source
Source
Bushing
Load-
Potential
Transformer