Procedure A: One Bypass Switch and
Two disconnect Switches
.
Verify from regulator nameplate that control circuit is
connected for proper regulated system voltage.
2 .
Set power switch to
OFF
and control switch to
OFF
.
3 .
Knife switches on back panel should be set with
V
(potential switch) (and
V
6
if present) closed (pushed
in) and
C
(CT shorting switch) open (pulled out). See
Figure 11.
4 .
Close source-load (SL) disconnect switch if available.
5 .
Close source (S) disconnect switch.
6 .
Set power switch to
INTERNAL
and control switch to
MANUAL
.
7 .
Lift raise-lower switch to operate tap-changer two or
three steps, then depress raise-lower switch to return
tap-changer to the neutral position. (These steps verify
that the mechanism is functional.) When on neutral, the
neutral light will glow continuously and position indica-
tor will point to zero (Neutral).
8 .
With regulator in neutral position, set control switch to
OFF
, set power switch to
OFF
, open
V
knife switch
(and
V
6
if present), and remove 6 A motor fuse.
.
Close load (L) disconnect switch.
0 .
Open bypass switch. The regulator is now energized.
.
Replace 6 A motor fuse, close
V
knife switch, and set
power switch to
INTERNAL
.
2 .
Refer to
Service Information S225-11-1 Voltage
Regulators, CL-6 Series Control Installation, Operation,
and Maintenance Instructions
for information on the
CL-6 voltage regulator control, including placing the
control into service and initial programming.
Procedure B: Regulator Bypass-
disconnect Switch
.
Verify from regulator nameplate that control circuit is
connected for proper regulated system voltage.
2 .
Set control switch to
MANUAL
and power switch to
EXTERNAL
.
3 .
Knife switches on back panel should be set with
V
(potential switch) (and
V
6
if present) open (pulled out)
and
C
(CT shorting switch) closed (pushed in). See
Figure 11.
4 .
Apply 120 V (or other voltage as indicated by the decal)
to external source terminals, if available. If not, proceed
to Step 7
,
below.
5 .
Lift raise-lower switch to operate tap-changer two or
three steps, then depress raise-lower switch to return
tap-changer to neutral position. (These steps verify
that the mechanism is functional.) When on neutral, the
neutral light will glow continuously and position indica-
tor will point to zero (Neutral).
6 .
Remove the voltage from external source terminals.
7 .
With regulator in the neutral position, set control switch
to
OFF
, set power switch to
OFF
, and remove 6 A
motor fuse.
8 .
For Delta applications only: Close source-load (SL)
disconnect switch.
.
Close regulator bypass-disconnect switch. The regula-
tor is now energized.
0 .
Replace 6 A motor fuse, close
V
knife switch (and
V
6
if present), open
C
knife switch, and set power switch
to
INTERNAL
.
S225-10-30
!