background image

S150-34-1

25

6.5  CONTROLS AND MEASUREMENTS

Five key buttons allow for local management of all of the relay's functions.
An 8-digit high brightness alphanumerical display shows the relevant readings 

(xxxxxxxx)

(see synoptic table fig.1)

FIG.1

MEASURES

MAX VAL

LastTr-X

TRIP NUM

ACT MEAS

Actual measuremant values

Max. values measured

Recording of last five events

N° of tripping for each function

Measurements

display

SET DISP

SETTINGS

F

RELAY

Display of setting

Display of configuration of output relay

Setting Program

display

PROGR

SETTINGS

F

RELAY

Setting of parameters

Configuration of output relays

Set Programming

PROG

TEST PRG

W/O TRIP

WithTRIP

Functional Test

Test with operation of signals and output relays

Test with operation of signals only

Test activation

by the key ENTER

Paramater scanning

by the key

SELECT

Parameter modification

by the key “+” “-”

Set validation

by the key ENTER

Scanning of

 the menus by

the key

“+” “-”

MODE

SELECT

ENTER

+     -

(*) Enabled only if input current is zero

(*)

(*)

ENTER/RESET

MODE SELECT

+

-

PROG.

The SELECT button chooses
which category of values within
the chosen mode to display

Pressing this button
progressively selects between
Measurements Display,
Setting Display, Programming,
and Test modes

When in Program mode, this
button stores the newly
selected value. If not in
Program mode and the relay
has tripped, this button resets
the relay and all output
contacts. If not tripped, this

The + and - buttons are used to
select the actual measurement
or display desired when in
Measurements Display or
Settings
Display modes. When in
Program mode, these buttons
increase or decrease the value

When in Program mode, and
when all input currents are
zero, pressing this recessed
button places the relay into
active programming mode,
allowing any or all of the relay’s
settings to be altered.

Содержание Low Impedance Bus Differential Relay M-LIB3

Страница 1: ...Protective Relays SALES AID M LIB3 Low Impedance Bus Differential Relay S150 34 1 October 1999 1999 Cooper Industries Inc New Issue 1 MODULAR LOW IMPEDANCE BUS PROTECTION TYPE M LIB3 OPERATION MANUAL...

Страница 2: ...__________ 20 6 Digital Low Impedance Differential Protection Relay M LID3_______________________________________________ 21 6 1 General Characteristic_________________________________________________...

Страница 3: ...imits 1 5 OUTPUTS LOADING Must be compatible with their declared performance 1 6 PROTECTION EARTHING When grounding is required carefully check its efficiency 1 7 SETTING AND CALIBRATION Carefully che...

Страница 4: ...nti static surface or on a conducting surface which is at the same potential as yourself e Store or transport the module in a conductive bag More information on safe working procedures for all electro...

Страница 5: ...or check zone feature without duplication of main CTs q Self contained isolator repeat relays switching at secondary of the zone input CTs q Self contained discrepancy alarm relays q Multivoltage powe...

Страница 6: ...3 M LID3 Numerical biased protection relay With the following features q Double circuit for Biased differential protection q Double circuit for unbiased differential protection q Double circuit for CT...

Страница 7: ...for interfacing with the differential protection relays q 1 Female connector socket for interconnection with other F C Rack Panels q 1 Power supply module The auxiliary power is supplied by a built i...

Страница 8: ...mpedance Bus Differential Relay 8 2 5 ACCESSORIES 2 5 1 CF1 Cable with female plug Female connector plug with multicore cable for connection between the terminals of the protection relays and the Zone...

Страница 9: ...S150 34 1 9 2 5 2 CFM Interconnection cable with Male and Female plugs Multicore cable terminated with one male and one female connector plugs for interconnection between F C Rack Panels...

Страница 10: ...lity level 40 In max 2 7 CURRENT TRANSFORMER REQUIREMENTS Current transformer requirements Minimum knee point voltage VK F In RT where F Accuracy limit factor 20 recommended In Main CT s rated seconda...

Страница 11: ...ule MC R Control Matrix MX7 5 Breaker Failure relay BF20 et cetera q One plug in module M BF3 for each incoming outgoing Feeder connected to the Busbar system q One plug in module M BC3 for each Bus C...

Страница 12: ...M LIB3 Low Impedance Bus Differential Relay 12 3 1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM...

Страница 13: ...S150 34 1 13 3 2 Application example As an example a double busbar system with two zones 10 feeders and one bus coupler is considered...

Страница 14: ...M LIB3 Low Impedance Bus Differential Relay 14...

Страница 15: ...inhibit the tripping of the differential element due to CT s saturation during external faults q Power Supply is fed to all the M BF3 modules from the Power supply unit included in the F C rack panel...

Страница 16: ...lay 16 Each of the 7 bays of the F C panel can accept either one module M BF3 or one module M BC3 q Current input burden each module In 1A 0 5 VA 0 5 In 5A on request q Power supply consumption each m...

Страница 17: ...S150 34 1 17 4 1 WIRING DIAGRAM M BF3 SCE1577...

Страница 18: ...s Differential Relay the trip coil of the Bus Coupler s Circuit Breaker is energized by both the zone trip signals It means that any fault on the bus bar system always trips the bus coupler q Power Su...

Страница 19: ...50 34 1 19 Each of the 7 bays of the F C panel can accept either one module M BF3 or one module M BC3 q Current input burden each module In 1A 0 5 VA 0 5 In 5A on request BACK SIDE M BC3 CARD F C PANE...

Страница 20: ...M LIB3 Low Impedance Bus Differential Relay 20 5 1 WIRING DIAGRAM M BC3 SCE1578...

Страница 21: ...IMPEDANCE DIFFERENTIAL PROTECTION RELAY TYPE M LID3 LOW IMPEDANCE BIASED DIFFERENTIAL RELAY TYPE M LID3 ENTER RESET MODE SELECT PROG dB PROG I R F MICROELETTRICA SCIENTIFICA MILANO ITALY BLOCK INPUT d...

Страница 22: ...SUPPLY The auxiliary power is supplied by a fully isolated and self protected built in interchangeable module Two options are available 24V 20 110V 15 a c 80V 20 220V 15 a c a b 24V 20 125V 20 d c 90V...

Страница 23: ...e incoming and outgoing currents When no fault inside the zone is experienced should be Id 0 Due to differences among the CTs and mostly to CT saturation when faults outside the zone make large throug...

Страница 24: ...ion the actual minimum operation level IS is dynamically adjusted in function of the actual through current IR according to the set coefficient 1R 2R IR 1IR IS IdS 1IR IR 2IR IS IdS 1R IR 1IR IR 2IR I...

Страница 25: ...scanning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MODE S...

Страница 26: ...Yellow LED PROG I R F q Flashing during the programming of the parameters or in case of Internal Relay Fault f Red LED Remote Trigger q Illuminated when the oscillography trigger input is activated g...

Страница 27: ...le at relay s level can be received at computer s level The transmission standard is RS485 converter 485 232 available with ModBus Jbus protocol Each relay is identified by its programmable address co...

Страница 28: ...SET plus one indirect operable key PROG see synoptic table a fig 1 a White key MODE when operated it enters one of the following operation modes indicated on the display MEASURES Reading of all the pa...

Страница 29: ...phase B dCxx xxn As above phase C IR xx xn Through current 0 99 9 per unit of the rated input current 6 13 3 LASTTRIP Display of the function which caused the tripping of the relay plus values of the...

Страница 30: ...the key SELECT while or are pressed Press key ENTER RESET to validate the set values 6 15 1 PROGRAMMING OF FUNCTIONS SETTINGS Mode PROG menu SETTINGS Production standard settings here under shown Dis...

Страница 31: ...ersa After having programmed all four relays press ENTER to validate the programmed configuration Display Description Is 1 Bias Differential element operates relay R1 eventually plus R2 R3 R4 as progr...

Страница 32: ...t code is displayed If at the next automatic test no internal fault is detected the display and R5 reset q Further operation of key SELECT instead of the TEST programs gives the indication of the vers...

Страница 33: ...groups of digits YY MMM or DD blinking The DOWN key operates as a cursor It moves through the groups of digits in the sequence YY MMM DD YY The UP key allows the user to modify the currently blinking...

Страница 34: ...M LIB3 Low Impedance Bus Differential Relay 34 6 19 WIRNG DIAGRAM M LID3 SCE1579...

Страница 35: ...00A m 0 1 1MHz q Electrical fast transient burst IEC61000 4 4 level 4 2kV 5 50ns 5kHz q HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1kV d m...

Страница 36: ...M LIB3 Low Impedance Bus Differential Relay 36 This page intentianally left blank...

Отзывы: