Cooper Low Impedance Bus Differential Relay M-LIB3 Скачать руководство пользователя страница 32

M-LIB3 Low Impedance Bus Differential Relay

32

6.16 MANUAL AND AUTOMATIC TEST OPERATION

6.16.1 Mode "TESTPROG" subprogram “W/O TRIP"

Operation of the yellow key activates a complete test of the electronics and the process routines.
All the LEDs are lit-on and the display shows (TEST RUN). If the test routine is successfully completed
the display switches-over to the default reading (

dA

xx.xx

n

). If an internal fault is detected, the display

shows the fault identification code and the relay R5 is de-energized. This test can be carried-out even
during the operation of the relay without affecting the relay tripping in case a fault takes place during
the test itself.

6.16.2 Mode "TESTPROG" subprogram "WithTRIP"

Access to this program  is enabled only if the current detected is zero (breaker open).
Pressing the yellow key the display shows "TEST RUN?". A second operation of the yellow key starts a
complete test which also includes the activation of all the output relays. The display shows
(TEST RUN) with the same procedure as for the test with W/O TRIP. During the normal operation the
relay continuously operates an auto test procedure. If any internal fault is detected during the auto test,
the relay R5 is de-energized, the relevant led is activated and the fault code is displayed. If at the next
automatic test no internal fault is detected the display and R5 reset.

q

 

Further operation of key SELECT instead of the TEST programs gives the indication of the version and
production date of the firmware.

WARNING

Running the 

WithTRIP

 test will operate all of the output relays. Care must be taken to ensure that no

unexpected or harmful equipment operations will occur as a result of running this test.
It is generally recommended that this test be run only in a bench test environment or after all dangerous output
connections are removed.

6.17 MAINTENANCE

No maintenance is required. Periodically a functional check-out can be made with the test procedures
described under  MANUAL TEST chapter. In case of malfunctioning please contact
Cooper Power Systems or the local Authorized Dealer mentioning the relay's Serial No reported in the label on
relays enclosure.

WARNING

In case of Internal Relay Fault detection, proceed as indicated :

q

 

If the error message displayed is one of the following “DSP Err”, “ALU Err” ,”KBD Err” ,”ADC Err”, switch off
power supply and switch-on again. If the message does not disappear send the relay to Cooper Power
Systems (or its local dealer) for repair.

q

 

If the error message displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”.

q

 

If message disappear please check all the parameters.

q

 

If message remains send the relay to Cooper Power Systems (or its local dealer) for repair.

Содержание Low Impedance Bus Differential Relay M-LIB3

Страница 1: ...Protective Relays SALES AID M LIB3 Low Impedance Bus Differential Relay S150 34 1 October 1999 1999 Cooper Industries Inc New Issue 1 MODULAR LOW IMPEDANCE BUS PROTECTION TYPE M LIB3 OPERATION MANUAL...

Страница 2: ...__________ 20 6 Digital Low Impedance Differential Protection Relay M LID3_______________________________________________ 21 6 1 General Characteristic_________________________________________________...

Страница 3: ...imits 1 5 OUTPUTS LOADING Must be compatible with their declared performance 1 6 PROTECTION EARTHING When grounding is required carefully check its efficiency 1 7 SETTING AND CALIBRATION Carefully che...

Страница 4: ...nti static surface or on a conducting surface which is at the same potential as yourself e Store or transport the module in a conductive bag More information on safe working procedures for all electro...

Страница 5: ...or check zone feature without duplication of main CTs q Self contained isolator repeat relays switching at secondary of the zone input CTs q Self contained discrepancy alarm relays q Multivoltage powe...

Страница 6: ...3 M LID3 Numerical biased protection relay With the following features q Double circuit for Biased differential protection q Double circuit for unbiased differential protection q Double circuit for CT...

Страница 7: ...for interfacing with the differential protection relays q 1 Female connector socket for interconnection with other F C Rack Panels q 1 Power supply module The auxiliary power is supplied by a built i...

Страница 8: ...mpedance Bus Differential Relay 8 2 5 ACCESSORIES 2 5 1 CF1 Cable with female plug Female connector plug with multicore cable for connection between the terminals of the protection relays and the Zone...

Страница 9: ...S150 34 1 9 2 5 2 CFM Interconnection cable with Male and Female plugs Multicore cable terminated with one male and one female connector plugs for interconnection between F C Rack Panels...

Страница 10: ...lity level 40 In max 2 7 CURRENT TRANSFORMER REQUIREMENTS Current transformer requirements Minimum knee point voltage VK F In RT where F Accuracy limit factor 20 recommended In Main CT s rated seconda...

Страница 11: ...ule MC R Control Matrix MX7 5 Breaker Failure relay BF20 et cetera q One plug in module M BF3 for each incoming outgoing Feeder connected to the Busbar system q One plug in module M BC3 for each Bus C...

Страница 12: ...M LIB3 Low Impedance Bus Differential Relay 12 3 1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM...

Страница 13: ...S150 34 1 13 3 2 Application example As an example a double busbar system with two zones 10 feeders and one bus coupler is considered...

Страница 14: ...M LIB3 Low Impedance Bus Differential Relay 14...

Страница 15: ...inhibit the tripping of the differential element due to CT s saturation during external faults q Power Supply is fed to all the M BF3 modules from the Power supply unit included in the F C rack panel...

Страница 16: ...lay 16 Each of the 7 bays of the F C panel can accept either one module M BF3 or one module M BC3 q Current input burden each module In 1A 0 5 VA 0 5 In 5A on request q Power supply consumption each m...

Страница 17: ...S150 34 1 17 4 1 WIRING DIAGRAM M BF3 SCE1577...

Страница 18: ...s Differential Relay the trip coil of the Bus Coupler s Circuit Breaker is energized by both the zone trip signals It means that any fault on the bus bar system always trips the bus coupler q Power Su...

Страница 19: ...50 34 1 19 Each of the 7 bays of the F C panel can accept either one module M BF3 or one module M BC3 q Current input burden each module In 1A 0 5 VA 0 5 In 5A on request BACK SIDE M BC3 CARD F C PANE...

Страница 20: ...M LIB3 Low Impedance Bus Differential Relay 20 5 1 WIRING DIAGRAM M BC3 SCE1578...

Страница 21: ...IMPEDANCE DIFFERENTIAL PROTECTION RELAY TYPE M LID3 LOW IMPEDANCE BIASED DIFFERENTIAL RELAY TYPE M LID3 ENTER RESET MODE SELECT PROG dB PROG I R F MICROELETTRICA SCIENTIFICA MILANO ITALY BLOCK INPUT d...

Страница 22: ...SUPPLY The auxiliary power is supplied by a fully isolated and self protected built in interchangeable module Two options are available 24V 20 110V 15 a c 80V 20 220V 15 a c a b 24V 20 125V 20 d c 90V...

Страница 23: ...e incoming and outgoing currents When no fault inside the zone is experienced should be Id 0 Due to differences among the CTs and mostly to CT saturation when faults outside the zone make large throug...

Страница 24: ...ion the actual minimum operation level IS is dynamically adjusted in function of the actual through current IR according to the set coefficient 1R 2R IR 1IR IS IdS 1IR IR 2IR IS IdS 1R IR 1IR IR 2IR I...

Страница 25: ...scanning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MODE S...

Страница 26: ...Yellow LED PROG I R F q Flashing during the programming of the parameters or in case of Internal Relay Fault f Red LED Remote Trigger q Illuminated when the oscillography trigger input is activated g...

Страница 27: ...le at relay s level can be received at computer s level The transmission standard is RS485 converter 485 232 available with ModBus Jbus protocol Each relay is identified by its programmable address co...

Страница 28: ...SET plus one indirect operable key PROG see synoptic table a fig 1 a White key MODE when operated it enters one of the following operation modes indicated on the display MEASURES Reading of all the pa...

Страница 29: ...phase B dCxx xxn As above phase C IR xx xn Through current 0 99 9 per unit of the rated input current 6 13 3 LASTTRIP Display of the function which caused the tripping of the relay plus values of the...

Страница 30: ...the key SELECT while or are pressed Press key ENTER RESET to validate the set values 6 15 1 PROGRAMMING OF FUNCTIONS SETTINGS Mode PROG menu SETTINGS Production standard settings here under shown Dis...

Страница 31: ...ersa After having programmed all four relays press ENTER to validate the programmed configuration Display Description Is 1 Bias Differential element operates relay R1 eventually plus R2 R3 R4 as progr...

Страница 32: ...t code is displayed If at the next automatic test no internal fault is detected the display and R5 reset q Further operation of key SELECT instead of the TEST programs gives the indication of the vers...

Страница 33: ...groups of digits YY MMM or DD blinking The DOWN key operates as a cursor It moves through the groups of digits in the sequence YY MMM DD YY The UP key allows the user to modify the currently blinking...

Страница 34: ...M LIB3 Low Impedance Bus Differential Relay 34 6 19 WIRNG DIAGRAM M LID3 SCE1579...

Страница 35: ...00A m 0 1 1MHz q Electrical fast transient burst IEC61000 4 4 level 4 2kV 5 50ns 5kHz q HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1kV d m...

Страница 36: ...M LIB3 Low Impedance Bus Differential Relay 36 This page intentianally left blank...

Отзывы: