2.4 F/C Rack Panel
19” 3U rack panel suitable to house up to seven plug-in modules type M-BF3 or M-BC3 including
back printed circuit board with :
q
Diodes for supply of the measurement bus of two Main Zones and one Check Zone
q
7 Female sockets for plug-in connection of the M-BF3 or M-BC3 modules.
q
7 Terminal boards with screw terminals for connection to the system.
q
1 Male connector socket for interfacing with the differential protection relays.
q
1 Female connector socket for interconnection with other F/C Rack Panels.
q
1 Power supply module:
The auxiliary power is supplied by a built-in interchangeable module fully isolated and self
protected. Two options are available
:
24V(-20%) / 110V(+15%) a.c.
80V(-20%) / 220V(+15%) a.c.
a) -
b) -
24V(-20%) / 125V(+20%) d.c.
90V(-20%) / 250V(+20%) d.c.
Before energizing the unit check that supply voltage is within the allowed limits.
Power consumption : nx 4W (n = number of modules M-BF3)
The unit can supply up to 12 modules M-BF3 plus two modules M-BC3 (one unit can supply two F/C Rack
Panels).
Содержание Low Impedance Bus Differential Relay M-LIB3
Страница 12: ...M LIB3 Low Impedance Bus Differential Relay 12 3 1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM...
Страница 14: ...M LIB3 Low Impedance Bus Differential Relay 14...
Страница 17: ...S150 34 1 17 4 1 WIRING DIAGRAM M BF3 SCE1577...
Страница 20: ...M LIB3 Low Impedance Bus Differential Relay 20 5 1 WIRING DIAGRAM M BC3 SCE1578...
Страница 34: ...M LIB3 Low Impedance Bus Differential Relay 34 6 19 WIRNG DIAGRAM M LID3 SCE1579...
Страница 36: ...M LIB3 Low Impedance Bus Differential Relay 36 This page intentianally left blank...