Instructional Leaflet
LCR 6200 Load Control Receiver
LCR 6200 Specifications
Communications
SelectComm 4020 VHF Paging Communication
Module
SelectComm 5020 900 MHz FLEX Paging
Communication Module
ZigBee Communication Module
Operating Requirements
Power Source:
240 VAC (+10% -20%)
Frequency:
60 Hz (±2%)
Consult Cooper Power Systems for 50 Hz
operation.
Temperature:
-40°F to +185°F (-40°C to +85°C)
Humidity:
0% to 95%, non-condensing
Relay Control
5 A at 120 VAC resistive, Form C
Housing
NEMA 3R injection-molded, UV-stabilized gray
polycarbonate plastic. Rain-tight per UL916.
Dimensions (Including Mounting Tabs)
5.95 H x 9.25 W x 3.22 D in.
(15.11 H x 23.50 W x 8.18 D cm)
Electrostatic Discharge
15 kV through Air per ANSI C12.1 (IEC 61000-4-2)
Surge Withstand Capability
Oscillatory:
6 kV @ 100 kHz waveform per
ANSI C12.1 (IEEE C62.41)
Fast Transient:
6 kV @ 1.2x50 μs - 8x20 μs waveform per
ANSI C12.1 (IEEE C62.41)
Wire Size Limits
This energy management device is designed, tested
and certified to UL Standard 916, which contains
allowances for field wiring system conductor sizing.
It is intended to be connected directly to the
equipment it is controlling, using the following wiring
requirements:
•
Use 12 AWG field wiring leads for installation with
8 AWG or 10 AWG branch-circuit conductors.
•
Use 18 AWG field wiring leads for installation with
12 AWG or smaller branch-circuit conductors.
In the event that this energy management device is
connected directly to a branch-circuit overcurrent
protection device, the following wire size limitations
apply:
•
Use 12 AWG wire for 25 A or smaller circuits.
•
Use 18 AWG wire for 7 A or smaller circuits.