background image

6

Instructional Leaflet

LCR 6200 Load Control Receiver

LCR 6200 Specifications

Communications

SelectComm 4020 VHF Paging Communication 
Module

SelectComm 5020 900 MHz FLEX Paging 
Communication Module

ZigBee Communication Module

Operating Requirements

Power Source:

240 VAC (+10% -20%)

Frequency:

60 Hz (±2%)
Consult Cooper Power Systems for 50 Hz 

operation.

Temperature:

-40°F to +185°F (-40°C to +85°C)

Humidity:

0% to 95%, non-condensing

Relay Control

5 A at 120 VAC resistive, Form C

Housing

NEMA 3R injection-molded, UV-stabilized gray 
polycarbonate plastic. Rain-tight per UL916.

Dimensions (Including Mounting Tabs)

5.95 H x 9.25 W x 3.22 D in.
(15.11 H x 23.50 W x 8.18 D cm)

Electrostatic Discharge

15 kV through Air per ANSI C12.1 (IEC 61000-4-2)

Surge Withstand Capability

Oscillatory:

6 kV @ 100 kHz waveform per 
ANSI C12.1 (IEEE C62.41)

Fast Transient:

6 kV @ 1.2x50 μs - 8x20 μs waveform per 
ANSI C12.1 (IEEE C62.41)

Wire Size Limits

This energy management device is designed, tested 
and certified to UL Standard 916, which contains 
allowances for field wiring system conductor sizing. 
It is intended to be connected directly to the 
equipment it is controlling, using the following wiring 
requirements:

Use 12 AWG field wiring leads for installation with 
8 AWG or 10 AWG branch-circuit conductors.

Use 18 AWG field wiring leads for installation with 
12 AWG or smaller branch-circuit conductors.

In the event that this energy management device is 
connected directly to a branch-circuit overcurrent 
protection device, the following wire size limitations 
apply:

Use 12 AWG wire for 25 A or smaller circuits.

Use 18 AWG wire for 7 A or smaller circuits.

Содержание LCR 6200

Страница 1: ...sent through the SelectComm and ZigBee communication modules No special test equipment or programming is required to install the LCR 6200 in the field The LCR 6200 addressing must be configured for your demand response system prior to operation CAUTION Observe precautions for handling electrostatic sensitive devices MISE EN GARDE Respectez les précautions de manipulation des dispositifs à décharge...

Страница 2: ...ated throughout the document SAFETY FOR LIFE SAFETY FOR LIFE Hazard Statement Definitions This document may contain four types of hazard statements DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not...

Страница 3: ...the wiring within a 1 2 liquid tight non metallic flexible conduit or make sure the wiring is close nippled into an approved junction box or wiring compartment All wiring connections are made to factory installed leads that are rated for 600 VAC 105 C No polarity requirements apply to the output leads 4 Locate and record the LCR address Install Code EUI 64 address and any other necessary informati...

Страница 4: ...he LCR receiver board for more than five seconds to instruct the ZigBee module to join the ZigBee network NOTE The commissioning process may take up to five minutes to complete When the commissioning process is complete the LCR Status LCD turns on solid and the ZigBee status of the LCR changes to Commissioned in the Yukon software LCR 6200 LEDs The LCR 6200 LEDs have the following meanings Load St...

Страница 5: ...to increment the control time by the configurable period of time For example if the configurable period of time is set to 30 seconds push the Test button four times to control for two minutes The relay control initiated by the Test button is implemented as a standard timed load control command zero delay and zero random extension This overrides any other currently implemented or delayed control Wh...

Страница 6: ...12 1 IEC 61000 4 2 Surge Withstand Capability Oscillatory 6 kV 100 kHz waveform per ANSI C12 1 IEEE C62 41 Fast Transient 6 kV 1 2x50 μs 8x20 μs waveform per ANSI C12 1 IEEE C62 41 Wire Size Limits This energy management device is designed tested and certified to UL Standard 916 which contains allowances for field wiring system conductor sizing It is intended to be connected directly to the equipm...

Страница 7: ...Cooper Power Systems 7 CT Y0 0398 SAFETY FOR LIFE ...

Страница 8: ...scriptions or safety notations LCR 6200 Load Control Receiver FCC COMPLIANCE STATEMENT This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to co...

Отзывы: