Cooper Power Systems
5
CT-Y0-0398
!
SAFETY
FOR LIFE
Test Button
The Test button, located on the LCR receiver board,
can perform the following functions.
Cancel Control and Power Detection at Power-On
Push and hold the Test button while applying power
to the unit to cancel any current control or cold load
pickup and bypass the power stability detection.
Test Relay Control
Push and release the Test button to control the relay
for a configurable period of time. Push the Test
button multiple times to increment the control time
by the configurable period of time.
For example, if the configurable period of time is set
to 30 seconds, push the Test button four times to
control for two minutes.
The relay control initiated by the Test button is
implemented as a standard timed load control
command, zero delay, and zero random extension.
This overrides any other currently implemented or
delayed control.
When controlling equipment such as well pumps or
air conditioning compressors, push the Test button
more than once to ensure that the control time is not
too short.
Commissioning
Push and hold the push Test button for more than
five seconds to instruct the ZigBee module to join the
ZigBee network.