background image

Cooper Power Systems

3

CT-Y0-0398

!

SAFETY

FOR LIFE

Installing the LCR 6200

Complete the following steps to install an LCR 6200:

1. Mount the LCR 6200 at the desired location, 

which is preferably a flat, non-vibrating 
surface.

The LCR enclosure has two pre-drilled mounting 
tabs. Cooper Power Systems recommends pan 
head screws up to 1/4” in size for mounting the 
LCR. The distance between the mounting holes is 
8.25 inches, and the diameter of the mounting 
holes is 0.3125 inches.

For a rain-tight rating, mount the LCR so that the 
“This Way Up” arrow on the label points up.

2. Remove electrical power from the AC circuits 

that are to supply power to the LCR and the 
load to be controlled.

3. Wire the LCR 6200 according to the wiring 

diagram located on the LCR cover.

Install the wiring within a 1/2” liquid-tight, non-
metallic, flexible conduit or make sure the wiring is 
close nippled into an approved junction box or 
wiring compartment.

All wiring connections are made to factory-
installed leads that are rated for 600 VAC, 105° C. 
No polarity requirements apply to the output 
leads.

4. Locate and record the LCR address, Install 

Code, EUI-64 address, and any other 
necessary information.

5. Apply electrical power to the LCR.
6. Commission the ZigBee module by 

performing the steps described in 

“Commissioning the ZigBee Module” on 
page 4

.

7. If desired, perform a test shed as described in 

the section 

“Test Button” on page 5

.

8. Close the LCR door, secure the latch, and 

install a utility seal.

WARNING:

Dangerous voltages are present. 

Multiple disconnects may be required to 
de-energize all circuits.

AVERTISSEMENT:

Présence de tensions 

dangereuses. Il pourrait être nécessaire de 
procéder à des débranchements multiples pour 
mettre tous les circuits hors tension.

Содержание LCR 6200

Страница 1: ...sent through the SelectComm and ZigBee communication modules No special test equipment or programming is required to install the LCR 6200 in the field The LCR 6200 addressing must be configured for your demand response system prior to operation CAUTION Observe precautions for handling electrostatic sensitive devices MISE EN GARDE Respectez les précautions de manipulation des dispositifs à décharge...

Страница 2: ...ated throughout the document SAFETY FOR LIFE SAFETY FOR LIFE Hazard Statement Definitions This document may contain four types of hazard statements DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not...

Страница 3: ...the wiring within a 1 2 liquid tight non metallic flexible conduit or make sure the wiring is close nippled into an approved junction box or wiring compartment All wiring connections are made to factory installed leads that are rated for 600 VAC 105 C No polarity requirements apply to the output leads 4 Locate and record the LCR address Install Code EUI 64 address and any other necessary informati...

Страница 4: ...he LCR receiver board for more than five seconds to instruct the ZigBee module to join the ZigBee network NOTE The commissioning process may take up to five minutes to complete When the commissioning process is complete the LCR Status LCD turns on solid and the ZigBee status of the LCR changes to Commissioned in the Yukon software LCR 6200 LEDs The LCR 6200 LEDs have the following meanings Load St...

Страница 5: ...to increment the control time by the configurable period of time For example if the configurable period of time is set to 30 seconds push the Test button four times to control for two minutes The relay control initiated by the Test button is implemented as a standard timed load control command zero delay and zero random extension This overrides any other currently implemented or delayed control Wh...

Страница 6: ...12 1 IEC 61000 4 2 Surge Withstand Capability Oscillatory 6 kV 100 kHz waveform per ANSI C12 1 IEEE C62 41 Fast Transient 6 kV 1 2x50 μs 8x20 μs waveform per ANSI C12 1 IEEE C62 41 Wire Size Limits This energy management device is designed tested and certified to UL Standard 916 which contains allowances for field wiring system conductor sizing It is intended to be connected directly to the equipm...

Страница 7: ...Cooper Power Systems 7 CT Y0 0398 SAFETY FOR LIFE ...

Страница 8: ...scriptions or safety notations LCR 6200 Load Control Receiver FCC COMPLIANCE STATEMENT This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to co...

Отзывы: