Cable entries (KLE);

Cable entries (KLE);

Cable entries (KLE);

Cable entries (KLE);

Cable entries (KLE);
blanking plugs

blanking plugs

blanking plugs

blanking plugs

blanking plugs

Generally, only certified cable entries and
blanking plugs may be used.

Flexible cables shall be used with
trumpet-shaped cable glands or other
suitable entries with additional pull-relief.

The directives for mounting applicable to
the cable entries fitted shall be observed.

When mounting cable entries of a lower IP
protection than that of the apparatus (see
page 8), the IP protection of the whole unit will
be reduced.

In order to establish the minimum protection
category, unused entry holes shall be closed
with a certified blanking plug.

Care has to be taken that when fitting the
cable entries, sealing inserts appropriate to
the cable diameter be used. In case of
sealing inserts that are cut out, it will have to
be ensured that the insert is properly
adapted to the cable diameter.

In order to ensure the required minimum
protection category, the cable entries will
have to be tightened down.

Overtightening might impair the
protection category.

6.4

Flange plates

Should flange plates have to be removed (e.
g. for drilling entry openings), attention will
have to be paid to the proper fit of the flange
plate  while mounting in order to maintain the
minimum protection category.

Metal flange plates shall be included in
the potential equalisation.

6.5

Closing the device/

Closing the device/

Closing the device/

Closing the device/

Closing the device/
cover closure

cover closure

cover closure

cover closure

cover closure

The switch toggle of the safety switches shall
be in ON position. When placing the cover
take care that the shaft of the switch engages
in the tappet hole of the switch toggle.

Any foreign matter shall be removed from
the apparatus.

To close the apparatus the enclosure cover
shall be closed using the internal square
spanner of the catch lock.

6.6

6.6

6.6

6.6

6.6

T

T

T

T

Taking into operation

aking into operation

aking into operation

aking into operation

aking into operation

Prior to taking the apparatus into operation,
the tests specified in the relevant national
regulations are to be carried out. Apart from
that, the correct functioning and installation of
the apparatus in accordance with these
operating instructions and other applicable
regulations shall be checked.

The improper operation of safety
switches may result in the invalidation of
the guarantee.

7

Maintenance/Servicing

The relevant national regulations which
apply to the maintenance/servicing of
electrical apparatus, shall be observed.

Before opening the enclosure make sure
that the apparatus is disconnected from
the supply, or take the appropriate
protective measures.

The required maintenance intervals depend
on the respective application and shall
therefore be determined by the user
dependent on the conditions of use.
When servicing the apparatus, particularly
those parts that are decisive for the type of
protection against explosion, shall be
checked (e. g. intactness of the enclosure,
cable glands, efficacy of the gaskets).

The reliable working of the cover lock and
the integrity of the padlocking device
shall be especially checked.

If during servicing repairs prove to be neces-
sary, section 8 of these operating instructions
shall be observed.

8

Repairs/Overhaul

Repairs/Overhaul

Repairs/Overhaul

Repairs/Overhaul

Repairs/Overhaul

Repairs may only be carried out with genuine
Cooper Crouse-Hinds / CEAG spare parts.

In case the switch base is damaged, only
its replacement will be permitted. In case
of doubt, the respective apparatus will
have to be returned for repair to Cooper
Crouse-Hinds / CEAG.

Modifications to the apparatus or changes of
its design are not permitted, except for the
mounting of additional cable entries in accor-
dance with the approval of the apparatus.

9

Disposal/Recycling

Disposal/Recycling

Disposal/Recycling

Disposal/Recycling

Disposal/Recycling

When the apparatus is disposed of, the
respective national regulations on waste
disposal shall be observed,
In order to facilitate the recycling of individual
components, plastic parts are provided with
the identification mark of the plastic material
used.

Subject to modifications or supplement of the
product range.

Safety switches, industrial design KO

All screws and/or nuts of the supply
terminals, also of those remaining vacant,
shall be tightened down.

Attention:
The cable lugs should be crimped onto the
cable in a workmanlike manner.

Содержание Crouse-Hinds CEAG KO

Страница 1: ...ra lingua della Comunit à Europea potete richiederla al vostro rappresentante Cooper Crouse Hinds CEAG Montagevejledningen kan oversættes til andre EU sprog og rekvireres hos Deres Cooper Crouse Hinds CEAG leverandør Indien noodzakelijk kan de vertaling van deze gebruiksinstructie in een andere EU taal worden opgevraagd bij Uw Cooper Crouse Hinds CEAG vertegenwoordiging Tarvittaessa tämän käyttöoh...

Страница 2: ... A 6p 7 1 2 6 Safety switch 315 A 6p 7 1 2 7 Safety switch 400 A 6p 7 1 2 8 Safety switch 630 A 6p 7 2 Safety instructions 6 3 Conformity with standards 6 4 Field of application 7 5 Application Properties 7 6 Installation 7 6 1 Mounting 7 6 2 Opening the device Electrical connection 7 6 3 Cable entry blanking plug 8 6 4 Flange plates 8 6 5 Closing the device cover closure 8 6 6 Taking into operati...

Страница 3: ...12 1 65 Nm Druckschraube der KLE M16 M20 2 50 Nm Druckschraube der KLE M25 3 50 Nm Druckschraube der KLE M32 M 63 5 00 Nm Druckschraube der Metall Ex e KLE M16 7 5 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M20 10 0 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M25 15 0 Nm z B Typ E1WF e Ex e Druckschraube der Metall Ex e KLE M32 25 0 Nm z B Typ E1WF e Ex e Druckschraube d...

Страница 4: ...en 6 2 Öffnen des Gerätes Elektrischer Anschluss Vor Öffnen der Geräte ist die Spannungs freiheit sicherzustellen bzw sind geignete Schutzmaßnahmen zu ergreifen Vor dem Öffnen ist der Schalter in EIN Stellung zu schalten Ein Schalten an der Achse des Schalter sockels bei geöffnetem Gehäuse ist nicht zulässig um den Schalter wieder korrekt schließen zu können Der elektrische Anschluss des Betriebs ...

Страница 5: ...r Reparatur zurückzugeben Umbauten oder Änderungen am Betriebsmit tel sind nicht gestattet ausgenommen ist das Anbringen von zusätzlichen KLE im Rahmen der Zulassung des Betriebsmittels 9 Entsorgung Wiederverwertung Bei der Entsorgung des Betriebsmittels sind die jeweils geltenden nationalen Abfall beseitigungsvorschriften zu beachten Zur Erleichterung der Wiederverwertbarkeit von Einzelteilen sin...

Страница 6: ...ogue version Sheet steel with powder coating 1 2 Safety switch 160 A Type Moeller P7 3 pole Rated voltage 400 V 50 60 Hz Rated current 160 A Perm short circuit back up fuse 160 A gG gL Switching capacity AC 23 160 A 1 2 2 Safety switch 250 A Type Moeller P7 3 pole Rated voltage 400 V 50 60 Hz Rated current 250 A Perm short circuit back up fuse 250 A gG gL Switching capacity AC 23 250 A 1 2 3 Safet...

Страница 7: ... be locked in the OFF position by means of 3 padlocks see Fig 1 shackle diameter of the padlocks up to 4 6 mm A built in locking device prevents the opening of the enclosure in the OFF position The data according to sections 3 and 4 shall be taken into account during use Applications other than those described are not permissible without a written declaration of consent from Messrs Cooper Crouse H...

Страница 8: ...he tests specified in the relevant national regulations are to be carried out Apart from that the correct functioning and installation of the apparatus in accordance with these operating instructions and other applicable regulations shall be checked The improper operation of safety switches may result in the invalidation of the guarantee 7 Maintenance Servicing The relevant national regulations wh...

Страница 9: ...0 A 1 2 4 Interrupteur de sécurité 630 A Type Moeller P7 3 pôles Tension nominale 400 V 50 60 Hz Courant nominal 630 A Fusible de court circuit adm placé en amont 800 A gG gL Puissance de coupure AC 23 630 A 2 2 2 2 2 Consignes de sécurité Consignes de sécurité Consignes de sécurité Consignes de sécurité Consignes de sécurité Les interrupteurs de sécurité ne conviennent pas à l emploi en atmosphèr...

Страница 10: ...e doit pas être endommagé Interrupteurs de sécurité type industriel KO 1 2 5 Interrupteur de sécurité 250 A Type ABB OETL 6 pôles Tension nominale 400 V 690 V 50 60 Hz Courant nominal 270 A Fusible de court circuit adm placé en amont 400 A 400 A gG gL Puissance de coupure AC 23 250 A 250 A 1 2 5 Interrupteur de sécurité 315 A Type ABB OETL 6 pôles Tension nominale 400 V 690 V 50 60 Hz Courant nomi...

Страница 11: ... en service Mise en service Avant la mise en service de l appareil les vérifications spécifiées dans les règlements nationaux individuels devront être exécutées De plus il faudra vérifier son fonctionnement et installation corrects en conformité avec ce mode d emploi et avec d autres règlements y applicables L utilisation incorrecte de ces commutateurs peut annuler la garantie 7 Maintien Entretien...

Страница 12: ...bH Cooper Crouse Hinds GmbH Cooper Crouse Hinds GmbH Cooper Crouse Hinds GmbH Neuer Weg Nord 49 D 69412 Eberbach Germany Phone 49 0 6271 806 500 Fax 49 0 6271 806 476 Internet www CEAG de E Mail Info ex ceag de GHG980700xP0001 D E F _ Auflage 0604 x ...

Отзывы: