Cooper CFDAU30 Скачать руководство пользователя страница 5

 

PR000-00-527-01 PINSTCFDAU30 

 

Page 5 of 18

 

Indications and Controls 

AC

General

Fire Mic

Fire Mic

CFDAU30

Addressable Voice Alarm System

BS5839 pt 8 & EN60849 Compliant

Message

Paging

Music

Level

Message

Paging

Music

Test

Reset

Access

DC

Fire Mic

Fault

Message

Supply

Fault

A

Amplifier

Open

Short

Earth

B

 

Supply Section Indicators 

AC 

 

Indicates healthy AC mains available. 

DC 

 

Indicates the battery supply is available. 

Fault 

 

Either the AC supply or DC supply is unavailable, or a fuse has ruptured. 

Amplifier Section Indicators (both channels are identical and independent) 

Open 

 

The CFDAU30 cannot see both end of line resistors for this amplifier 

channel. 

Short 

 

The CFDAU30 has detected a short on this amplifier channel. 

Earth 

 

The CFDAU30 has detected an earth fault on this amplifier channel. 

Access Section. 

 

Fire Mic   

Lights green when the fireman’s microphone is activated. 

Message 

Lights when a stored message is playing, Green for test, Yellow for the Alert 
Message and RED for the Evacuate message. 

Paging 

 Lights green when the paging microphone is in use. 

Music 

 Lights green when the music channel is open, (no other inputs in use). 

 

Test 

 This is a recessed push button, pressing this starts the test message 
broadcasting to the speakers. 

Reset 

 This recessed push button cancels any message playing (this will not cancel 
messages triggered from the fire alarm if the trigger is still active) the 
message always plays to the end of the current cycle once Reset. 

Fault Section. 

General 

 This lights when the CFDAU30 detects any fault in its operation. 

Fire Mic 

 Lights if there is any fault with the fireman’s microphone or cables to the 
microphone. 

Message 

 Lights if the message store in the CFDAU30 has detected a corruption. 

Level Controls 

Fire Mic 

 Sets the Level of the fireman’s Microphone, capped after commissioning. 

Message 

 Sets the level of the stored messages in the Cooper DAU, capped after 
commissioning 

Page 

Sets the level of the paging microphone input to the DAU 

Music 

Sets the level of the music to the Speakers.  

Содержание CFDAU30

Страница 1: ...CFDAU30 Voice Alarm System Installation and Maintenance Manual Cooper Lighting and Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL 44 0 1302 321541 FAX 44 0 1302 303220...

Страница 2: ...ommended for all public buildings and multi story buildings over four floors by BS5588 In public buildings it s not possible to fire drill the public as they visit the premises infrequently so systems...

Страница 3: ...e system designed to be used by the controlling officer 2 Message Generator this has three messages all messages latch until reset from either the front panel recessed button or from the cancel button...

Страница 4: ...s follows Weekly Broadcast the test message to all zones and check speaker operation microphones should be checked for operation if fitted record results in the site log Monthly Trigger the fire alarm...

Страница 5: ...e is playing Green for test Yellow for the Alert Message and RED for the Evacuate message Paging Lights green when the paging microphone is in use Music Lights green when the music channel is open no...

Страница 6: ...nits are distributed around a site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a un...

Страница 7: ...line Resistors e Crimped Battery Link Lead f Black jumper header to Enable Fire Microphone Monitoring Using the HEX key supplied remove the front cover Verify the following items are present 1 2 off...

Страница 8: ...ved fill the hole with a good quality cable gland 18 knockouts are provided 8 on the top face from left to right Speaker Network A Speaker Network B Fault Fire alarm Interface Fire Microphone connecti...

Страница 9: ...ed for the fire alarm interface loudspeakers fireman s microphone paging background music equipment and slave amplifiers please refer to the relevant sections later in this manual Note that correct ca...

Страница 10: ...and 1 hour operation 2 number 12V 17AH batteries are required these will need to be fitted in an external battery enclosure the monitored charger in the Cooper CFDAU30 is capable of charging and monit...

Страница 11: ...le speakers for CFDAU30 MUST have a thermal fuse to disconnect the speaker if it is in the area in fire and a DC blocking capacitor fitted typically the capacitor is 2 2uF 250V DC The wiring goes thro...

Страница 12: ...ction point see earlier in this manual preferred types are screened soft skin cables such as FP200 although MICC can be used Cable Length Chart The following table shows the maximum cable run to achie...

Страница 13: ...the top on the Cooper CFDAU30 the Au pin is at the bottom of the block The CFDAU30 is shipped as standard with the monitoring of the Fire Microphone DISABLED to enable the monitoring fit the jumper su...

Страница 14: ...n isolator and can be hard or soft addressed by the Cooper addressable panels CFDAU30 is fully monitored and controlled by any Cooper Fire addressable Fire Panels NOTE MESSAGES WILL ALWAYS PLAY TO THE...

Страница 15: ...messages can be independently adjusted using the front panel recessed control marked MESSAGES the messages Override paging and music when operated the level of the individual messages can be altered...

Страница 16: ...limiter to prevent clipping of the CFDAU30 and corrects for poor microphone technique The UNDM1 provides busy indication and first come first served logic for cascading microphones Microphone connect...

Страница 17: ...ted when mains fails in line with BS5839pt8 to preserve battery life The level of the paging microphone can be independently adjusted using the front panel recessed control marked MUSIC NOTE If music...

Страница 18: ...E Sensitivity 6dBV to 4dBV Ptt Type 5V to access Power 24V nominal 100mA self resetting fuse Fire Interface Inputs 3 off isolated 12V to 33V Alert Evacuate Reset Outputs 1 Relay open on fault 30V 1A M...

Отзывы: