The CFDAU30 delivers clear, intelligible voice alarm messages which ensures reliable and constant life 

safety protection for both people and property. 

It is well documented that only 13% of people react to bells, whilst 70% react to a voice message. 

 

 

The CFDAU30 has been developed to draw the minimum of current in standby conditions and mutes the 

music when the AC supply fails, the unit then draws 60mA quiescent current allowing the use of 3.2AH 

commodity SLA batteries for full compliance with BS5839 part 8. 

The speaker lines are monitored using a low current DC system, which is continuous, and works with 

the music playing. Faults reported are open, short and earth faults. Each speaker fitted to Cooper 

CFDAU30 must have a DC blocking capacitor fitted. The use of DC monitoring allows all cable types 

(MICC and soft skin) to be used with the system. 

Music sources can be plugged directly into the DAU, and the level of this can be set using a remote DC 

volume control. When used with a paging microphone, the music ducks and restores gently after paging. 

Priorities 

The Cooper CFDAU30 has six fixed priorities for the inputs as follows:- 

1. 

Fire Microphone, this is the highest priority input on the system, designed to be used by 

the controlling officer. 

2. 

Message Generator, this has three messages, all messages latch until reset from either 

the front panel recessed button, or from the cancel button on the fire microphone or by the 

RESET input from the Fire alarm input. Messages are prioritised in the following order: 

a.  EVAC- Triggered from the fire alarm interface or from the fireman’s microphone, top 

priority message. 

b.  ALERT- Triggered from the fire alarm interface or from the fireman’s microphone, 

second priority message. 

c.  TEST- Triggered from the front panel or from the fireman’s microphone, this is the 

lowest priority message. 

3. 

Page Input, this is the fifth priority input, designed for non-emergency functions such as 

reception paging. 

4. 

Music Input, this is the lowest priority input and automatically selected when no other input 

is exerting a priority, if not used turn the level control on the front panel fully anticlockwise. 

Operation 

The Cooper CFDAU30 is fully automatic in operation; the only user controls available once the unit has 

been commissioned are the front panel Reset and Test buttons. Pressing the test button will broadcast 

the test message to the speaker circuits and latch until the Reset button is pressed. 

The Cooper CFDAU30 has fully compliant fault monitoring when correctly installed and commissioned, if 

any status indicators are illuminated YELLOW (except the Message ACCESS Led) call service to 

Содержание CFDAU30

Страница 1: ...CFDAU30 Voice Alarm System Installation and Maintenance Manual Cooper Lighting and Safety Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB TEL 44 0 1302 321541 FAX 44 0 1302 303220...

Страница 2: ...ommended for all public buildings and multi story buildings over four floors by BS5588 In public buildings it s not possible to fire drill the public as they visit the premises infrequently so systems...

Страница 3: ...e system designed to be used by the controlling officer 2 Message Generator this has three messages all messages latch until reset from either the front panel recessed button or from the cancel button...

Страница 4: ...s follows Weekly Broadcast the test message to all zones and check speaker operation microphones should be checked for operation if fitted record results in the site log Monthly Trigger the fire alarm...

Страница 5: ...e is playing Green for test Yellow for the Alert Message and RED for the Evacuate message Paging Lights green when the paging microphone is in use Music Lights green when the music channel is open no...

Страница 6: ...nits are distributed around a site it is essential all units are on the same mains phase as they are classified TEN 230V powering from different phases can mean a 440V potential can be present in a un...

Страница 7: ...line Resistors e Crimped Battery Link Lead f Black jumper header to Enable Fire Microphone Monitoring Using the HEX key supplied remove the front cover Verify the following items are present 1 2 off...

Страница 8: ...ved fill the hole with a good quality cable gland 18 knockouts are provided 8 on the top face from left to right Speaker Network A Speaker Network B Fault Fire alarm Interface Fire Microphone connecti...

Страница 9: ...ed for the fire alarm interface loudspeakers fireman s microphone paging background music equipment and slave amplifiers please refer to the relevant sections later in this manual Note that correct ca...

Страница 10: ...and 1 hour operation 2 number 12V 17AH batteries are required these will need to be fitted in an external battery enclosure the monitored charger in the Cooper CFDAU30 is capable of charging and monit...

Страница 11: ...le speakers for CFDAU30 MUST have a thermal fuse to disconnect the speaker if it is in the area in fire and a DC blocking capacitor fitted typically the capacitor is 2 2uF 250V DC The wiring goes thro...

Страница 12: ...ction point see earlier in this manual preferred types are screened soft skin cables such as FP200 although MICC can be used Cable Length Chart The following table shows the maximum cable run to achie...

Страница 13: ...the top on the Cooper CFDAU30 the Au pin is at the bottom of the block The CFDAU30 is shipped as standard with the monitoring of the Fire Microphone DISABLED to enable the monitoring fit the jumper su...

Страница 14: ...n isolator and can be hard or soft addressed by the Cooper addressable panels CFDAU30 is fully monitored and controlled by any Cooper Fire addressable Fire Panels NOTE MESSAGES WILL ALWAYS PLAY TO THE...

Страница 15: ...messages can be independently adjusted using the front panel recessed control marked MESSAGES the messages Override paging and music when operated the level of the individual messages can be altered...

Страница 16: ...limiter to prevent clipping of the CFDAU30 and corrects for poor microphone technique The UNDM1 provides busy indication and first come first served logic for cascading microphones Microphone connect...

Страница 17: ...ted when mains fails in line with BS5839pt8 to preserve battery life The level of the paging microphone can be independently adjusted using the front panel recessed control marked MUSIC NOTE If music...

Страница 18: ...E Sensitivity 6dBV to 4dBV Ptt Type 5V to access Power 24V nominal 100mA self resetting fuse Fire Interface Inputs 3 off isolated 12V to 33V Alert Evacuate Reset Outputs 1 Relay open on fault 30V 1A M...

Отзывы: