Chapter 8: Troubleshooting
Series SPB Audio Boosters Manual, Revision A
8-2
When there are no trouble conditions detected on the Series SPB Audio Booster, the AC LED
and DC LED indicator always remains ON and the TROUBLE LED indicator always remains
OFF. When a trouble condition is detected, the AC LED indicator remains ON and the
TROUBLE LED indicator always remains ON.
Figures 8-1 and 8-2 show the location of all trouble location LED indicators within the Series
SPB Audio Booster panels. Table 8-1 cross-references the trouble location LED indicators on the
mother board to the proper troubleshooting procedure.
NOTE: When D73 TBL LED indicator is ON, indicating a panel Trouble, at least one of the other
yellow LED indicators is also ON, indicating the trouble location.
Table 8-1. Trouble LED Procedure Cross Reference
D73
LED
(Yellow)
Trouble Description
Troubleshooting
Procedure
D73
Main Trouble Indicator
------
D11 AC LED
“OFF”
No DC Power to the mother Board from the Power
Supply (SPBPS).
Procedure A
(section 8.2.1)
D49 BAT TRB
Battery voltage is below 18.5 VDC or battery is
missing.
Procedure B
(section 8.2.2)
D51 AC TRB
AC power input voltage missing from TB1.
Procedure C
(section 8.2.3)
D79 AUX TRB
External 1/2W EOLR missing when Jumper JP8 is
removed.
Procedure D,
(section 8.2.4)
D77 AMP TRB
Amplifier failure or jumpers J1 and J1A (SPB160) or
J1B (SPB-80/4) are not installed incorrectly.
Procedure E
(section 8.2.5)
D78 EXP
SHORT
Expansion Circuit is Shorted
Procedure F
(section 8.2.6)
D87 EXP OPEN
Expansion Circuit is Open
Procedure G
(section 8.2.7)
D100GF
Ground Fault Trouble
Procedure H
(section 8.2.8)
D25 AUD1
SHORT
Audio 1 Notification Appliance Circuit is Shorted
Procedure I
(section 8.2.9)
D30 AUD1
OPEN
Audio 1 Notification Appliance Circuit is open
Procedure J
(section 8.2.10)
D21 AUD2
SHORT
Audio 2 Notification Appliance Circuit is Shorted.
(SPB-160 Only)
Procedure K
(section 8.2.11)
D18 AUD2
OPEN
Audio 2 Notification Appliance Circuit is open.
(SPB-160 Only)
Procedure L
(section 8.2.12)
D56 STRB1
SHORT
Strobe Notification Appliance Circuit is shorted.
(SPB-80/4 Only)
Procedure M
(section 8.2.13)
D53 STRB1
OPEN
Strobe Notification Appliance Circuit is open.
(SPB-80/4 Only)
Procedure N
(section 8.2.14)
D67 STRB2
SHORT
Strobe Notification Appliance Circuit is shorted.
(SPB-80/4 Only)
Procedure O
(section 8.2.15)
D69 STRB2
OPEN
Strobe Notification Appliance Circuit is open.
(SPB-80/4 Only)
Procedure P
(section 8.2.16)
Before performing any of the following troubleshooting procedures, make sure
that you read, understand, and follow the preliminary troubleshooting information
at the beginning of this “troubleshooting” chapter.
Содержание SAFEPATH SPB-160
Страница 6: ...Series SPB Audio Boosters Manual Revision A vi This page is left blank intentionally...
Страница 8: ...Series SPB Audio Boosters Manual Revision A viii This page is left blank intentionally...
Страница 10: ...Series SPB Audio Boosters Manual Revision A x This page is left blank intentionally...
Страница 22: ...Chapter 3 Overview Series SPB Audio Boosters Manual Revision A 3 6 This page is left blank intentionally...
Страница 60: ...Chapter 4 Installation Series SPB Audio Boosters Manual Revision A 4 38 This page is left blank intentionally...
Страница 78: ......
Страница 85: ...Series SPB Audio Boosters Manual Revision A 11 1 11Battery Calculation Worksheet...