CEAG Notlichtsysteme GmbH
9
Mounting and Operating Instructions
1903 LED CG-S
3.6
Operational Safety
Observing the stated safety instructions and regulations can avoid damage to property and
people when working with the luminaire.
4
Technical Data
Input voltage:
220V/240 V AC, 50Hz, 176-275V DC
Current consumption battery operation: 12 mA
Connection power mains operation
5,5 VA / 3,03 W
(apparent power/active power)):
Enclosure:
Plastic material, white colour, RAL 9010
Weight:
1280g
Type of mounting:
ceiling mounting, vertical wall mounting
Supply terminals:
2,5 mm²
Perm. ambient temperature:
-10°C...+40°C
Insulation class:
II
Degree of protection:
IP 21
5
Installation and function
The exit luminaires 1903 LED CG-S are suitable for operation on CEAG emergency lighting
systems acc. to EN 50 172, DIN VDE 0100-718 and V DIN VDE 0108-100 . The advanced
switching and monitoring mode is only available in combination with CEAG CG-S-technolo
gy.
Содержание CEAG 1903 LED CG-S
Страница 1: ......
Страница 12: ...400 71 860 069 A XXX 03 10 WK...